Abstract
The dynamic characteristic evaluation is an important prerequisite for safe and reliable operation of the medium-voltage DC integrated power system (MIPS), and the dynamic state estimation is an essential technical approach to the evaluation. Unlike the electromechanical transient process in a traditional power system, periodic change in pulse load of the MIPS is an electromagnetic transient process. As the system state suddenly changes in the range of a smaller time constant, it is difficult to estimate the dynamic state due to periodic disturbance. This paper presents a dynamic mathematical model of the MIPS according to the network structure and control strategy, thereby overcoming the restrictions of algebraic variables on the estimation and developing a dynamic state estimation method based on the extended Kalman filter. Using the method of adding fictitious process noise, it is possible to solve the problem that the linearized algorithm of the MIPS model is less reliable when an abrupt change occurs in the pulse load. Therefore, the accuracy of the dynamic state estimation and the stability of the filter can be improved under the periodic disturbance of pulse load. The simulation and experimental results confirm that the proposed model and method are feasible and effective.
Keywords
Medium-voltage DC integrated power system; pulse load; dynamic state estimation; extended Kalman filter; fictitious process noise
THE vessel integrated power system means integrating the dynamical system of a traditional ship with its electrical system to provide electric energy for the propulsion system, shipborne equipment and daily service loads. It serves the function of central control and comprehensive utilization of energy sources, and it has advantages of improving the design of overall ship, increasing the system efficiency and reducing the noise. It was a trend towards information and intelligence [
Dynamic state estimation is to use the data measured from multiple sections for estimating the system state variables, and the extended Kalman filter (EKF) is useful for the nonlinear system estimation with advantages of simple operation and quick calculation. As phasor measurement units and advanced communication facilities are widely used in power systems, it is possible to develop a fast-response and robust tool for dynamic state estimation. At present, the dynamic state estimation of land power system is mostly applied for the AC system and the optimal estimation of its linear ordinary differential equation [
Studies on the MIPS and its estimation have just started. But most state estimation methods on an AC/DC hybrid system refer to the static state estimation at the present time [
In this paper, a mathematical model of the MIPS is established according to the topology of the system and the control strategy of the equipment, and a dynamic state estimation method is proposed based on the EKF, thereby solving the problem of algebraic variables on the estimation. The addition of fictitious process noise (FPN) to the system model at the point of abrupt change of the pulse load will improve the estimation accuracy and the filter stability under the periodic disturbance. The simulation and experimental results prove the effectiveness of the model and algorithm.

Fig. 1 Structure of MIPS.
The pulse load is connected to the DC busbar directly and releases a large amount of power during a short period, which makes strict demands on the vessel power system. The operation characteristics of the pulse load are shown in

Fig. 2 Characteristics of pulse load. (a) Rectangular-wave pulse load. (b) Triangular-wave pulse load.
It is necessary to establish a mathematical model for the equivalent load circuit of the MIPS. As shown in

Fig. 3 Equivalent load circuit of MIPS.
By Kirchhoff’s Law, the state equation of DC voltage in the equivalent load is written in per-unit value as follow:
(1) |
where p is the derivative, p=d/dt. If the peak values of the rated AC voltage and current of the generator are chosen as the base quantities, the term 3/2 in (1) is the calculated result of P [
There is a need to establish a mathematical model of the excitation system of the generator group. To keep the DC busbar voltage constant and make the rectifier generators produce the output power according to the ratio of their rated power, the excitation system uses the traditional droop control strategy to control the output power. As the droop control does not depend on the designated main generator to regulate the voltage, it is possible to prevent the system from breaking down due to a fault in the main generator in a master-slave control mode, and meanwhile, to decrease its dependency on the communication system and improve the reliability of the transmission system [
(2) |
where ki is the droop coefficient of the excitation system in the
(3) |
The result of can be calculated by (2) and (3). It means that the parallel rectifier generators will output the power according to their ratio of rated power.

Fig. 4 Excitation system under droop control.
According to the control law expressed in (2), the difference between and Edc0 goes through the proportional-integral (PI) controller and produces the excitation voltage Efi, which can keep the DC voltage constant and make the output power of the rectifier generators distributed equally according to their rated capacity. For the
(4) |
In [
(5) |
(6) |
(7) |
(8) |
(9) |
(10) |
(11) |
(12) |
(13) |
(14) |
(15) |
where ; and are the transient open-circuit time constants of the generator in d- and q-axes, respectively; is the time constant of the rectifier circuit; and are the transient voltages of the generator in d- and q-axes, respectively; and are the currents of the generator in d- and q-axes, respectively; xdi and xqi are the reactance of the generator in d- and q-axes, respectively; and are the transient reactance of the generator in d- and q-axes, respectively; and are the sub-transient reactance of the generator in d- and q-axes, respectively; is the commutation reactance; ri is the stator resistance; rdci and xdci are the equivalent rectification resistance and reactance, respectively; E1i is the equivalent voltage; and , and are the commutation conduction angle, the phase angle of the equivalent voltage, and the phase angle between the current and the voltage, respectively.
Equations
The 4m+1 dimensional state variable vector x and the 7m dimensional algebraic variable vector y of the system are: ;. Thus, the differential-algebraic equations
(16) |
There are some difficulties in the direct application of Kalman filter to the state-space model expressed by (4)-(15). This is because most of the state variables are fictitious and immeasurable, and the state equation of the model contains quite a few algebraic variables. In (4)-(15), algebraic variables are quite complex because they involve the correlation between the state variables and the correlation between the algebraic variables, which will lead the state equation to be of strong nonlinearity. The EKF is a fundamental approach for the estimation of the nonlinear system, which can be used to estimate the dynamic state of the MIPS in this paper. The basic principle of EKF is to obtain the predicted value of state variable at the next moment from the linearized state equations and use the measured value to modify the predicted value [
1) Euler’s formula is often used to convert the differential-algebraic
(17) |
where the subscript k is the position of the estimation point; is the process noise; and is the time step. The smaller the time step is, the higher accuracy the filter has.
Thus, the state estimation model can be expressed as:
(18) |
where zk is the measurement equation; vk is the measurement noise whose mean value is zero; and Qk and Rk are the positively definite covariance matrices.
2) Taylor’s series expansion of the state equation is carried out around and to obtain the following:
(19) |
where the superscript + represents the posteriori estimation; ; ; ; ; and .
Because , the incorporation of the two in (19) and the elimination of the item lead to:
where , and I is the unit matrix. The known signal and the noise signal are defined as:
(20) |
3) With E representing the expected value, the initialization of the filter and the estimation error covariance can be expressed as follows:
(21) |
(22) |
4) For , it is necessary to take the following steps.
Step 1: calculate the partial derivative matrices.
(23) |
Step 2: perform the time update of the state estimation and estimation error covariance matrices.
(24) |
where the superscript represents the priori estimation.
Step 3: linearize the measurement equation zk=h(xk,vk) around and and calculate the matrices , .
Step 4: perform the measurement update of the state estimation and estimation error covariance matrices.
(25) |
Step 5: take as an initial variable for the estimated value , and use the Newton iteration method to solve the algebraic equation so as to update the algebraic variable . The steps include: ① solve the residual error and Jacobian matrix ; ② modify the algebraic variable ; ③ use the modified algebraic variables and repeat the above two steps until each element in dg reaches the given accuracy.
According to (24), the EKF depends on the currently estimated value to predict the state variables at the next moment, and the use of Euler method to discretize the differential equations for state prediction is to take the first two terms out of the Taylor series expansion at the point [
At this point, the addition of FPN makes the EKF focus on the measurements but not the system model in the abrupt change of pulse load. After a short-time iteration, the system model becomes reliable again, and the FPN is removed to improve the filter performance. According to the theoretical analysis of the compensation for modeling errors by the FPN in Section 5.5 of [
1) If in (24) is small, the covariance may not increase much between time samples. In the example 5.3 of [
(26) |
2) If , the steady solution of (26) is zero. As shown in (25), the zero value of will result in Kk=0. The zero value of Kk means that the equation for in (25) will not involve any measured value. The measured value zk will be completely ignored in the computation of . That is because the measurement noise covariance Rk (assumed to be greater than zero) will always be larger than the process noise . The insensitivity of the filter to the measured value will lead to the sluggish response of the filter.
3) If is large, then the covariance will constantly increase between time samples, that is, will always be larger than . When converging, will converge to a larger value, which will make Kk converge to a larger value as well. Here, Kk with larger value means that the measurement update for in (25) will include a more important measured value, on which the filter will put greater emphasis.
To verify the proposed mathematical model, a turbine generator unit and a diesel generator unit are used as an example. A simulation model and a mathematical model are built in PSCAD/EMTDC. The diagrams of the simulation model and the control system of generator are shown in Figs.

Fig. 5 Diagram of simulation model.

Fig. 6 Diagram of control system of generator. (a) Excitation control. (b) Speed control.
The rated capacities of the two generators are 24 MW and 6 MW, respectively, whose droop coefficients are 0.085 and 0.340, respectively, and . The base values of voltage and current of the 24 MW generator (the
To verify these two models, it is necessary to analyze the dynamic characteristic of the system when an abrupt change occurs in the load. The rated voltage of the DC busbar Edcr is 6000 V. The resistive load is Ω. The operation power P suddenly drops from 9 MW to 3 MW at 10 s.

Fig. 7 Dynamic characteristics of MIPS during abrupt change of load. (a) Voltage of two models. (b) Current of two models. (c) DC component of voltage of two models. (d) DC component of current of two models.
Reference [
The operation power P is 3 MW, but the other parameters are kept unchanged. To verify the dynamic characteristic of the system during the sudden change of the DC busbar voltage, the Edcr controlled by the excitation system can be assumed to rise from 5000 V to 6000 V suddenly at 10 s.

Fig. 8 Dynamic characteristics of MIPS during abrupt change of DC voltage controlled by excitation system. (a) Voltage of two models. (b) Current of two models. (c) DC component of voltage of two models (d) DC component of current of two models.
According to the comparison of the above-mentioned results, both the models produce almost the same results in a steady state. But with the transient errors within the permissible range of engineering application, the mathematical model is accurate enough to describe the dynamic characteristics, so it can be used for dynamic state estimation.
The method based on the EKF is adopted for the dynamic state estimation. The measurement vector is [Ef1, Ef2, Idc1, Idc2, Edc].
The initial value of the EKF is based on the information obtained in advance. The closer it is to the true value, the faster the filter converges. The initial values of state and algebra variables are determined as the steady solution worked out by the mathematical model. The initial value of the covariance matrix of estimation error is and the initial value of the covariance matrix of process noise is . The Section 13.1 in [

Fig. 9 DC busbar voltage of MIPS. (a) Under rectangular-wave pulse load. (b) Under triangular-wave pulse load.

Fig. 10 Output current of

Fig. 11 State variables of

Fig. 12 State variables of
From Figs.

Fig. 13 Comparison of errors of Edc. (a) Under rectangular-wave pulse load. (b) Under triangular-wave pulse load.
According to

Fig. 14 Comparison of errors of Edc after using FPN. (a) Under rectangular-wave pulse load. (b) Under triangular-wave pulse load.
It is clear that the method of adding FPN can significantly reduce the estimation error at the sudden-change point of the pulse load and can maintain the accuracy of estimation at other positions in the meanwhile. To compare the estimation effects at the sudden-change point of the pulse load, Edc of the rectangular-wave pulse load is taken for an example. As shown in

Fig. 15 Estimation under sudden change of pulse load. (a) Without FPN. (b) With FPN.
In the whole range of estimation in Figs.
(27) |
where xa1 is the index of the measurement errors; xa3 and xa2 are the indexes of the estimation errors calculated with and without the FPN, respectively; xei is the estimated value; xri is the true value; xmi is the measured value; and n is the number of estimation points.
To compare the estimation effects at the sudden-change point of pulse load in Figs.
From the analysis above, the filter without the use of FPN behaves well in the whole range of estimation, but there will be an unacceptable oscillation, increase or decrease near the point of abrupt change. The use of FPN can reduce the estimation error caused by the periodic change of the pulse load and can improve the stability of the filter. The mean value of the calculation time spent at each estimation point is about 0.03 ms through the calculation on the simulation platform Windows equipped with a 4 GB memory and the fourth-generation CPU i5.
According to the topology and control strategy of the MIPS, this paper presents a dynamic mathematical model of the system. In order to accurately estimate the operation state of the system, a dynamic state estimation method based on the EKF is proposed. The method can be used to deal with complex algebraic variables in the proposed model, which is very applicable for the MIPS. A periodic change in power of the pulse load is called electromagnetic transient process. The time constant which becomes smaller due to a sudden change in the system state will greatly affect the estimation. The use of the FPN at the sudden-change point of pulse load can reduce the interference of the pulse load with the filter, and increase the estimation accuracy and the stability. The proposed dynamic state estimation method is verified by the simulation. Using the FPN, the method can solve the problem that the linearized algorithm of the MIPS model is less reliable when an abrupt change occurs in the pulse load.Thus the estimation accuracy can be improved under the periodic disturbance of pulse load, which will lay a foundation for an accurate dynamic state estimation of the MIPS with pulse load.
References
W. Ma, “A survey of the second-generation vessel integrated power system,” in Proceedings of the International Conference on Advanced Power System Automation and Protection, Beijing, China, Oct.2011, pp. 1-8. [百度学术]
W. Ma, “The integrated power system in warship,” in Proceedings of the 5th International Marine Electrotechnology Conference, Shanghai, China, Sept. 2003, pp. 2-7. [百度学术]
IEEE Recommended Practice for 1 to 35 kV Medium Voltage DC Power Systems on Ships, IEEE Std. 1709-2010, 2010. [百度学术]
J. F. Hansen and F. Wendt, “History and state of the art in commercial electric ship propulsion, integrated power systems, and future trends,” Proceedings of the IEEE, vol. 103, no. 12, pp. 2229-2242, Dec.2015. [百度学术]
G. Wang, R. Xiao, and X. Wu, “Analysis of integrated power system with pulse load by periodic orbit,” IEEE Transactions on Plasma Science, vol. 47, no. 2, pp. 1345-1351, Feb.2019. [百度学术]
D. Simon, Optimal State Estimation: Kalman, H∞, and Nonlinear Approaches. New York: Wiley, 2006. [百度学术]
J. Zhao, A. Gómez-Expósito, M. Netto et al., “Power system dynamic state estimation: motivations, definitions, methodologies, and future work,” IEEE Transactions on Power Systems, vol. 34, no. 4, pp. 3188-3198, Jul.2019. [百度学术]
A. G. Phadke and T. Bi, “Phasor measurement units, WAMS, and their applications in protection and control of power systems,” Journal of Modern Power Systems and Clean Energy, vol. 6, no. 4, pp. 619-629, Jul.2018. [百度学术]
J. Yang, W. Wu, W. Zheng et al., “A sparse recovery model with fast decoupled solution for distribution state estimation and its performance analysis,” Journal of Modern Power Systems and Clean Energy, vol. 7, no. 6, pp. 1411-1421, Nov.2019. [百度学术]
G. Anagnostou and B. C. Pal, “Derivative-free Kalman filtering based approaches to dynamic state estimation for power systems with unknown inputs,” IEEE Transactions on Power Systems, vol. 33, no. 1, pp. 116-130, Jan.2018. [百度学术]
J. Sun and H. Grotstollen, “Averaged modelling of switching power converters: reformulation and theoretical basis,” in Proceedings of 23rd Annual IEEE Power Electronics Specialists Conference, Toledo, Spain, Jun.-Jul. 1992, pp. 1165-1172. [百度学术]
N. Xia, H. B. Gooi, S. Chen et al., “Decentralized state estimation for hybrid AC/DC microgrids,” IEEE Systems Journal, vol. 12, no. 1, pp. 434-443, Mar.2018. [百度学术]
P. Ling, X. Kong, C. Fang et al., “Novel distributed state estimation method for the AC-DC hybrid microgrid based on the Lagrangian relaxation method,” The Journal of Engineering, vol. 2019, no. 18, pp. 4932-4936, Aug.2019. [百度学术]
X. Kong, Z. Yan, R. Guo et al., “Three-stage distributed state estimation for AC-DC hybrid distribution network under mixed measurement environment,” IEEE Access, vol. 6, pp. 39027-39036, Jul.2018. [百度学术]
D. Bosich, G. Sulligoi, E. Mocanu et al., “Medium voltage DC power systems on ships: an offline parameter estimation for tuning the controllers’ linearizing function,” IEEE Transactions on Energy Conversion, vol. 32, no. 2, pp. 748-758, Jun.2017. [百度学术]
J. Jatskevich and S. D. Pekarek, “Numerical validation of parametric average-value modeling of synchronous machine-rectifier systems for variable frequency operation,” IEEE Transactions on Energy Conversion, vol. 23, no. 1, pp. 342-344, Mar.2008. [百度学术]
S. L. Woodruff, L. Qi, and M. J. Sloderbeck, “Hardware-in-the-loop experiments on the use of propulsion motors to reduce pulse-load system disturbances,” in Proceedings of2007 IEEE Electric Ship Technologies Symposium, Arlington, USA, May 2007, pp. 1-7. [百度学术]
H.-F. Li, J. Liang, Z. Yun et al., “Optimized operation mode of coordination between the flywheel energy storage and generators for pulsed loads in micro-grid,” in Proceedings of2017 2nd International Conference on Power and Renewable Energy (ICPRE), Chengdu, China, Sept. 2017, pp. 732-736. [百度学术]
P. Kundur, Power System Stability and Control. New York: McGraw-Hill Companies, 1994. [百度学术]
R. Wang, Q. Sun, and Y. Gui. “Exponential-function-based droop control for islanded microgrids,” Journal of Modern Power Systems and Clean Energy, vol. 7, no. 4, pp. 899-912, Jul.2019. [百度学术]
W. Ma, A. Hu, D. Liu et al., “Stability of a synchronous generator with diode-bridge rectifier and back-EMF load,” IEEE Transactions on Energy Conversion, vol. 15, no. 4, pp. 458-463, Dec.2000. [百度学术]
M. Sakui and H. Fujita, “An analytical method for calculating harmonic currents of a three-phase diode-bridge rectifier with DC filter,” IEEE Transactions on Power Electronics, vol. 9, no. 6, pp. 631-637, Nov.1994. [百度学术]