Abstract
As the structures of multiple branch lines (MBLs) will be widely applied in the future flexible DC distribution network, there is a urgent need for improving system reliability by tackling the frequent non-permanent pole-to-pole (P-P) fault on distribution lines. A novel fault restoration strategy based on local information is proposed to solve this issue. The strategy firstly splits a double-ended power supply network into two single-ended power supply networks through the timing difference characteristics of a hybrid direct current circuit breaker (HDCCB) entering the recloser. Then, a method based on the characteristic of the transient energy of fault current is proposed to screen the faulty branch line in each single-ended power supply network. Also, a four-terminal flexible DC distribution network with MBLs is constructed on PSCAD to demonstrate the efficacy of the proposed strategy. Various factors such as noise, fault location, and DC arc equivalent resistance are considered in the simulation model for testing. Test results prove that the proposed strategy for fault restoration is effective, and features high performance and scalability.
THE Chinese government has proposed to reach a carbon peak by 2030 and carbon neutrality by 2060 [
Unlike the AC distribution network, faults on the DC line cause more serious consequences. Insulated gate bipolar transistors (IGBTs) in the multi-module multi-level converter (MMC) are subjected to high fault current, increasing their probability of damage [
The key of traditional fault restoration is to reliably determine the fault property (permanent fault (PF) or NPF) [
For the distribution network, a large number of distributed loads are often configured, and the structures of MBLs are required to meet the demand [
There are two fault categories on DC lines: P-G fault and pole-to-pole (P-P) fault. Under the same system condition, a P-P fault usually results in a higher fault current, which could potentially cause more damages to the system. Therefore, the fault restoration strategy proposed in this paper mainly focuses on the P-P faults.
The main contributions of this paper are as follows.
1) The proposed strategy can distinguish the fault property (PF or NPF) and the DC line fault type (P-G or P-P), and identify specific faulty branch lines.
2) The proposed strategy is suitable for the scenarios with MBLs and is more suitable for distribution networks.
3) The proposed strategy is based on local information and does not need communication. It can be used as a backup for the communication-based fault restoration strategy.
4) The proposed strategy can be used in conjunction with other fault restoration strategies to provide a better fault restoration effect for the system.
The rest of this paper is organized as follows. In Section II, the topology of the flexible DC distribution network and the wavelet transform (WT) algorithm are analyzed. In Section III, a novel fault restoration strategy is proposed for P-P faults, which is based on the split method to construct an independent radiation network. The complete scheme of the proposed fault restoration strategy is given in Section IV. In Section V, the simulation model is established, and the performance of the proposed restoration strategy is evaluated under different fault conditions. Finally, the conclusions and potential limitations are presented in Section VI.
In China, the need for MBLs has been demonstrated, especially by the operation of relevant DC projects [

Fig. 1 Diagram of a flexible DC distribution network with MBLs.
The distribution network shown in
Considering that the communication of the protection device may fail, the protection device will not work normally. It is necessary to configure single-ended protection (no communication) as a backup for the pilot protection. Aiming at the frequent transient faults of overhead lines, our research group has studied a single-ended protection scheme suitable for the full cycle of the fault. The scheme is divided into two steps. ① Fault detection: build boundary fast protection with the help of CLRs, and issue trip instructions to HDCCB in areas A1 and B4. ② Fault restoration: judge the fault property (PF or NPF) and specific faulty lines. A large amount of literature focuses on fault detection, but the research on fault restoration is merely investigated.
The traditional fault restoration strategies can only judge the fault property and cannot determine faulty lines in MBL situations. For this paper, a novel fault restoration strategy for the flexible DC distribution network with MBLs is proposed, which aims to accurately identify faulty lines.
When a P-P fault occurs on f2 in L142, the equivalent circuit of the fault loop is illustrated in

Fig. 2 Equivalent circuit of fault loop when a P-P fault occurs.
(1) |
(2) |
where Udc and Iload are the DC rate voltage and rate current; A is the variable coefficient; is the time constant of the fault loop; is the grid angular frequency; is the initial phase angle before failure; and is the initial phase angle after a fault.
The equivalent circuit shown in
(3) |
In general, is much greater than , so the frequency of the current is mainly restricted by .
Taking a demonstration project as an example, we assume mH, , and . A P-P fault occurs at the outlet side of the MMC, and the fo corresponding to the discharging current of the sub-module capacitor of the MMC is near 50 Hz. Whereas the current of the AC system feeding into the fault point through the MMC corresponds to Hz.
The high-frequency components of fault currents decay rapidly in the time domain. The WT algorithm has a good time-domain resolution in the high-frequency band of the signal and is ideally suitable for the analysis of extracting these fast-varying high-frequency components [
(4) |
where is the mother wavelet function; a is the scale factor; and b is the translation factor.
In engineering practice, all the signals are discrete, which can be extracted by discrete WT (DWT). For a discrete signal sample ao(k), the smoothing approximation coefficient aj(k) and detail coefficient dj(k) of the
(5) |
where h0 and h1 are the low-pass filter and high-pass filter, respectively.
In this paper, the DbN-DWT is selected to extract the frequency components of the fault current. The higher the order N, the smaller the high-frequency coefficient of the signal, and the more concentrated the signal energy. Meanwhile, the smaller the order N, the rougher the frequency band division, and the more dispersed the energy. Combining the effectiveness and computational efficiency, the DbN-DWT is adopted and a 4-layer decomposition is performed to extract feature quantities of the fault signal, as shown in

Fig. 3 Feature quantities of fault signal extracted by DdN-DWT.
For a multi-source network with multiple MMCs, during the fault restoration process, the faulty line will be fed by the MMC at both ends of the line. The current of the MMC fed to the faulty point will be superimposed. Meanwhile, the mutual influence between the MMCs will be increased, which poses a challenge to the fault restoration strategy based on single-ended quantities. The proposed fault restoration strategy mainly includes the split method and faulty branch line identification method based on the transient energy of fault current.
A split method is proposed, which splits the double-ended power supply network into two mutually independent single-ended power supply networks, as shown in

Fig. 4 Two independent single-ended power supply networks under an NPF situation when L14 is split. (a) Single-ended power supply network at MMC1 side. (b) Single-ended power supply network at MMC2 side.

Fig. 5 Two independent single-ended power supply networks under a PF situation when L14 is split. (a) Single-ended power supply network at MMC1 side. (b) Single-ended power supply network at MMC2 side.
The split method proposed in this subsection needs to be used in conjunction with reclosing. By closing the HDCCBs at both sides of the line according to a certain sequence, the fault information can be collected to determine the faulty branch line.
According to the above analysis, the reclosing process can be divided into the following two steps.
1) Close the HDCCB in area A1 at the MMC1 side. Subsequently, MMC1 will feed current into the line, while HDCCB in area B4 at the MMC2 side is still in the open state. If the fault property is NPF, it means that there is no fault point on the line before HDCCB in area A1 is closed. The MMC1 side has completed the reclosing operation, as shown in
2) After a certain fixed time delay, close the HDCCB in area B4 at the MMC1 side. The MMC2 side will also complete the reclosing operation. Thus, both MMC1 and MMC2 will supply the power normally, and the system will return to its normal state, as shown in
If the fault property is PF, the fault still exists before the HDCCB in area A1 is closed. The fault point and the MMC1 are in the same fault circuit, as shown in
The procedure of the split method is as follows, and the logic sequence diagram is shown in

Fig. 6 Logic sequence diagram of fault restart split method.
1) Step 1: close the HDCCB of the power sending end, and judge the fault property (PF or NPF). For the PF, the corresponding HDCCB needs to be actuated, while for the NPF, the MMC1 side completes a fault restoration.
2) Step 2: perform the same operation on the power receiving end.
In
When a PF occurs on line L14, the influence of the transition resistance is not considered. During the fault restoration period, when the HDCCB in area A1 at the MMC1 side is closed, the fault current will only be affected by the impedance value of the fault loop, which is positively correlated with the distance to the fault. The fault current provided by the single-ended power supply network varies with the distance from the MMC1 to the fault point, as shown in

Fig. 7 Schematic diagram of fault current provided by single-ended power supply network at MMC1 side.
In the NPF case, the current characteristics are more obvious and the characteristics of the current energy are considered to distinguish the faulty branch line. Use DbN-DWT to extract the low-frequency information of the fault current. And the sum of squares of wavelet coefficients is used to characterize the transient energy of fault current in a fixed frequency band time window.
Take the PF at point f2 in L142 as an example. The HDCCB in areas A1 and B4 will receive a trip command to remove the entire line of L14 after a fault occurs. At this point, the fault restoration phase is activated and the HDCCB in area A1 at the MMC1 side needs to be closed as the first step of fault restoration. The fault current is fed from MMC1 to f2 through areas A1 and A2. Using the transient energy of the fault current as that of the characteristic quantity, L142 is quickly identified as a faulty line. Subsequently, the HDCCB in area A2 will complete the tripping behaviour immediately, isolate the MMC1 and f2 perfectly, and prevent the formation of electrical circuits. Since the HDCCB in area A2 is in the open state, MMC1 does not feed f2, as shown in

Fig. 8 Description of fault restoration using proposed restoration strategy. (a) First step of fault restoration. (b) Second step of fault restoration.
Following the same logic, the second step of the fault restoration is started. The HDCCB in area B4 at the MMC2 side completes the closing operation. The fault current in the fault circuit is fed from MMC2 to f2 through areas B4, B3, and B2. Using the same judgment method, L142 is judged to be a faulty branch line, and the DCCB in the B2 area acts, as shown in
Under the influence of noise and other special conditions, the transient energy of fault current calculated for the end of the line L141 and the first section of L142 may overlap. The overlapping part belongs to the unreliable area of the identification result, which may cause the HDCCB on the non-faulty line to malfunction, as shown in

Fig. 9 Diagram of trusted area of fault restoration strategy.
Three functions must be met in the proposed strategy: ① the fault property can be distinguished, and the power supply can be restored smoothly under NPF; ② the type of fault can be identified, and only the faulty branch line for P-P faults is judged; ③ in the case of a PF fault, the faulty branch line can be determined, and a trip command can be sent to the corresponding HDCCB to remove the fault again. As the strategy focuses on P-P faults, a fault type screening criterion is added within this section.
According to Section III, when the HDCCB in area A1 at the MMC1 side is closed, regardless of whether the fault exists, MMC1 and MMC2 are isolated and cannot pass current. Therefore, the voltage information is used in this subsection to determine the fault property. For the NPF, the fault disappears before entering the fault restoration, while in the PF, the clamping voltage of the fault point is still affected after the fault restoration.
Take the PF at point f2 of L142 as an example. When entering the first step of the fault restoration, the HDCCB in area A1 is closed, and the existence of point f2 limits the voltage rise of the circuit. On the contrary, when an NPF fault occurs on L142, fault point f2 does not exist. The voltage of the circuit increases to the rated voltage with the closing of HDCCB in area A1. Similar characteristics also exist in the second step of fault restoration. In summary, the characteristic of voltage rise degree is used to distinguish PF and NPF.
In this subsection, 0.85Ubus is chosen as the rectification value, and Ubus is the normal operating bus voltage. A single voltage data point cannot reliably distinguish PF and NPF. Therefore, the 3 ms data window is chosen for the simulation process.
The reclosing criterion can be expressed as:
(6) |
where kreclose is the reliability coefficient, which is selected as 0.85 [
The proposed strategy is mainly applicable to P-P faults, so further identification of the fault type is required. For a P-P fault at point f2 on L142, the positive and negative lines constitute a faulty circuit. The positive and negative currents are equal and much larger than the steady-state current. However, when a P-G fault occurs at point f2 on L142, the current of the fault pole increases rapidly and is much larger than the steady-state current. Though the current of the non-fault pole will be affected by the fault pole, it will remain the value near the steady-state current. Therefore, the relationship between the positive current and the negative current can be used to accurately distinguish the fault type.
Assume that the positive and negative currents are x1 and x2, respectively, which are shown in (7). The calculation method of the Pearson correlation coefficient of x1 and x2 is shown in (8). When the criterion of (9) is satisfied, a P-P fault occurs in the line. While when the criterion (10) is satisfied, a P-G positive line fault occurs; otherwise, a P-G negative line fault occurs.
(7) |
(8) |
(9) |
(10) |
where and are the instantaneous values of the positive and negative currents collected, respectively; and are the average values of the positive and negative currents collected, respectively; and is the setting value, which is selected as 0.9.
For P-P faults, the positive and negative currents are the same, and the ideally calculated Pearson correlation coefficient is always 1. However, for a P-G positive line fault, the positive pole current continues to increase, and its current value x1 is greater than 0; while the negative pole current value x2 fluctuates up and down around 0. Since , the Pearson correlation coefficient is less than 1.
The theoretical interval of the Pearson correlation coefficient in statistics is [-1,1]. When a P-P fault occurs on the line, the Pearson correlation coefficient is approximately 1. Considering the Harsh working conditions such as noise, a margin region is set to improve the reliability of the judgment result, as shown in

Fig. 10 Margin region of Pearson correlation coefficient.
If the coefficient , it is considered as a P-P fault, and it is recorded as . However, if the coefficient is not in that range and , it is considered as a P-G positive line fault; otherwise, it is considered as a P-G negative line fault. Whether there is a P-G positive or P-G negative line fault, it is recorded as .
According to the analysis in Section III, in a single-ended power supply network, its fault current can be approximately equated to a smooth curve only related to the fault distance, as shown in
The calculation method of the transient energy of fault current in a fixed frequency band is as follows: select DbN-DWT to obtain the scale coefficient, and calculate the sum of squares of the scale coefficient in the time window of 5 ms. It can be expressed as:
(11) |
where Ei is the transient energy of fault current of the
Take the HDCCB in area A1 at the MMC1 side as an example. Assume that EsetA1, EsetA2, EsetA3, and EsetA4 are the setting values of A1, A2, A3, and A4, respectively, which are the transient energies of fault current corresponding to the fault at the end of the line. There is a step difference in the current of each branch line, and the transient energy of fault current will further amplify this difference characteristic. Thus, the setting values of A1, A2, A3, and A4 have a certain degree of selectivity. And the action setting value is the setting value multiplied by a reliability factor.
When the fault occurs in the areas of L141, L142, L143, and L144, the corresponding fault transient energy is recorded as EA1, EA2, EA3, and EA4. Then, it is compared with the action setting value of each branch line. If it is greater than the action setting value, it is judged as a faulty branch, and a trip command is issued to the HDCCB of the line. Afterwards, the HDCCB in area B4 at the MMC2 side is closed immediately. If EA1 is greater than kset EsetA1, L141 is considered to be a faulty branch line, and HDCCB in the A1 area will trip. The corresponding criterion can be expressed as:
(12) |
Under PF faults, the fault current curve is considered a continuous one. The corresponding transient energy curve of the fault current can also be regarded as a continuous one. To ensure the maximum protection range, the value of the reliability coefficient can be reduced. In the most ideal case, kset can be set to be 1.
Following the same logic, EsetB1, EsetB2, EsetB3, and EsetB4 are assumed to be the setting values of B1, B2, B3, and B4, respectively. The corresponding criterion can be expressed as:
(13) |
If the criteria of (12) and (13) are met, the corresponding Ai (, 2, 3, 4) and Bi (, 2, 3, 4) belong to an internal PF. The corresponding HDCCB needs to be tripped, which is recorded as and . If the criteria are not met, an external PF occurs on the corresponding branch line, which is recorded as and .
There is a time interval between the HDCCBs in areas A1 and B4. The length of the time interval depends on the fault detection, HDCCB action, and DC arc extinction, as shown in

Fig. 11 Timing coordination diagram of fault restoration.
Based on the above analysis, a logical block diagram of the proposed strategy is shown in

Fig. 12 Logic diagram of proposed strategy.

Fig. 13 Logic diagram of HDCCB signal in corresponding area under PF condition.
It can be observed from

Fig. 14 Flowchart of fault restoration strategy based on transient energy of fault current.
A multi-terminal flexible DC distribution network with MBLs described in [

Fig. 15 Schematic diagram of a multi-terminal flexible DC distribution network with MBLs.
In the fault restoration phase, the HDCCB in the area A1 at the MMCB2 side will be closed first. For NPFs, the line voltage will quickly increase to 0.85Ubus and then stabilize to Ubus. However, for PFs, the line voltage will be limited to very low levels, approximately zero, due to the presence of the fault point.
The time window chosen for this subsection is 3 ms, so the basic setting value is chosen to be 51. In the case of an NPF, the climbing degree of the line voltage is greater than 51, while in the case of a PF, the climbing degree of the line voltage is less than 51.

Fig. 16 Judgment result of PF and NPF.
As mentioned above, after a P-P occurs, the positive and negative currents are in the same fault circuit, and the calculated Pearson correlation coefficient is always 1. However, the change trends of the positive and negative currents are different, and the corresponding Pearson correlation coefficient is less than 1. Meanwhile, the longer the data window, the greater the difference between the Pearson correlation coefficients corresponding to P-P and P-G faults. The Pearson correlation coefficient can correctly distinguish P-P and P-G faults, and the results are shown in

Fig. 17 Judgment results of P-P and P-G faults.
If the judgment result is a P-P fault, the proposed strategy needs to be used to identify the faulty branch line.
Take L14 as an example. By performing the fault simulation at different locations in the line L14, the action setting values (ksetEsetA1, ksetEsetA2, ksetEsetA3, ksetEsetA4, ksetEsetB1, ksetEsetB2, ksetEsetB3, and ksetEsetB4) corresponding to L141, L142, L143, and L144 after a P-P Fault are calculated and shown in
In the fault restoration phase, the HDCCB in area A1 at the MMCB2 side will be closed first. EA1, EA2, EA3, and EA4 are calculated according to (11), respectively, and are compared with the setting values in

Fig. 18 Judgment results of faulty branch line during fault restoration. (a) Judgment results of area A1 at MMCB2 side after reclosing. (b) Judgment results of area B4 at MMCE1 side after reclosing.
After a fixed time delay, the HDCCB in area B4 at the MMC2 side starts to be closed. EB1, EB2, EB3, and EB4 are calculated according to (11), and are compared with the setting values in
Further, the P-P faults are tested for different fault locations, and the identification results are shown in Tables
Note: 0 (L141) represents that the fault occurs on the L141, and the number 0 represents the length from the fault point to the first section of L141.
Ideally, the full length of the line can be identified according to the principle of the action setting values. For a 25 km line, when the length of the faulty line is 20 km, the ratio of the calculated value of the transient energy of fault current to the setting value is greater than 1.08. This means that the protection range of the line in 80% of the area has a certain selectivity. Therefore, the transient energy of fault current can effectively identify internal and external PFs. The adaptability and robustness of the proposed strategy for different situations are further considered.
Anti-noise analysis is carried out on the identification results of internal and external PFs, and the noise is Gaussian white noise. The signal-to-noise ratios of 10, 20, 30, 40, 50 dB, and infinity (no noise) are selected as variables, respectively. No matter what the signal-to-noise ratio is, the transient energy of fault current does not fluctuate greatly during the fault restoration process. Even if the signal-to-noise ratio is 10 dB, the faulty branch line L142 can still be correctly identified, as shown in

Fig. 19 Identification results of faulty branch line under different signal-to-noise ratios.
The Gaussian white noise is essentially random data with the mean value of zero and non-zero variance. The mean value of zero will not affect the calculation results of (11). With a noise level of 10 dB, the results are all correct. Therefore, the proposed strategy has a strong anti-noise ability.
According to (12), L142 is judged to be a faulty branch line, the corresponding HDCCB in area A2 will receive a trip instruction. During the fault restoration process, the amplitude of the fault current corresponding to different conditions is different, and the time required to extinguish the DC arc after the HDCCB action is also different. Ideally, before the HDCCB in area B4 at the MMCE1 side is closed, the arc in area A2 is completely dissipated. However, in most cases, there is still a small amount of DC arc in area A2, which will affect the identification results of the faulty lines during the restoration process of the HDCCB in area B4 at the MMCE1 side.
In PSCAD, the nature of the opening state of HDCCB is equivalent to connecting a large resistor (1 ) in series in the system. The DC arc is simulated by adjusting the value of the series resistance. Further, the identification results of fault areas are analyzed when the equivalent resistance of HDCCBs is different. According to the static characteristics of the arc of the improved Mayr model, when the current is less than 0.5 kA, the arc equivalent resistance will be greater than 12 .
Take a P-P fault at L143 as an example. The smaller the equivalent resistance of the HDCCB, the larger the corresponding DC arc. When the DC arc is too large, it is easy to cause the fault to recur. In this paper, after treclose(PR), the feed-in current to the fault point at the MMCB2 side is less than 0.5 kA, so the minimum equivalent resistance of the arc is considered to be 12 .
In this subsection, the DC equivalent resistance is replaced by a constant resistance, and the minimum equivalent DC arc resistance of the HDCCB is 10 . According to the identification results in

Fig. 20 Identification results of fault areas under different DC arc equivalent resistance. (a) Identification results of fault areas A1, A2, A3, and A4. (b) Identification results of fault areas B1, B2, B3, and B4.
Taking area B1 as an example, the two main influencing factors, i.e., the fault location and the DC arc equivalent resistance, are considered simultaneously. The identification results of the area B1 under different DC arc equivalent resistances and fault locations are shown in

Fig. 21 Identification results of area B1 under different DC arc equivalent resistances and fault locations.
Assume that other parameters do not change, and only the number of sub-modules in the MMC is changed. The number varies from 38 to 200 and the identification results of the fault areas are shown in

Fig. 22 Identification results of fault areas under different numbers of sub-modules in MMC. (a) Identification results of fault areas A1, A2, A3, and A4. (b) Identification results of fault areas B1, B2, B3, and B4.
When the number of sub-modules is 38, it can be observed that there is an error in the identification result at the PS side, and the calculation result is approximately equal to the threshold value. The decrease of the number of sub-modules increases the transient energy of fault current appropriately, but the increased value is limited. The results demonstrate that the proposed restoration strategy can meet the requirements, and the minimum number of sub-modules can be used as a parameter in the actual engineering calculation of the setting value.
The network shown in
Assuming that other parameters do not change, and only the control mode of MMCE1 is changed, the identification results of the fault areas are shown in
The proposed strategy focuses on models containing MBLs. This strategy only involves the coordination problem of MBLs between two MMCs. And the strategy is independent of the line type (overhead line or cable), the number of branch lines, and the number of MMCs. Therefore, the proposed strategy can be easily extended to various topology scenarios with MBLs and has good scalability.
Suppose a P-P fault occurs at line L16, the main protection of line L14 malfunctions, and the areas A1 and B4 give a trip command to the corresponding HDCCBs. To analyze the applicability performance of the proposed strategy under this operating condition, three cases are set up according to the different entry reclosing times of lines L14 and L16.
1) Case 1: L16 enters the fault restoration phase first, and after a fixed time delay, L14 enters the fault restoration phase.
2) Case 2: L16 and L14 enter the fault restoration phase at the same time.
3) Case 3: L14 enters the fault restoration phase first, and after a fixed time delay, L16 enters the fault restoration phase.
The fixed time delay chosen for this subsection is 2 ms.
The identification results of the fault area under different cases are shown in

Fig. 23 Identification results of fault areas under different cases. (a) Identification results of fault areas A1, A2, A3, and A4. (b) Identification results of fault areas B1, B2, B3, and B4.
Generally, the probability of a non-permanent P-P fault in a flexible DC distribution system with MBLs is high. As the traditional fault restoration strategy has its limitation in determining the faulty branch line, a novel fault restoration strategy is proposed to overcome such shortcomings for better distinguishing the faulty branch lines.
The proposed strategy cooperates with the reclosing strategy of the HDCCB. A split method is used to convert a double-ended supply network into two independent single-ended power supply networks. Then, a faulty line criterion is proposed based on the transient energy of fault current, which can be used to reliably identify faulty branch lines using only local information. Furthermore, the proposed strategy can also be used in conjunction with other fault restoration strategies.
It is worth pointing out that the proposed strategy still has some potential limitations: ① it cannot be applied to P-G fault in which the transition resistance is uncertain; ② it cannot be applied to the scenarios where the converter has multiple feeders; ③ it needs to further analyze and improve the unreliable area.
References
Y. Qi, S. Nicholas, J. He et al., “The policy-driven peak and reduction of China’s carbon emissions,” Advances in Climate Change Research, vol. 11, no. 2, pp. 65-71, Jun. 2020. [Baidu Scholar]
L. Zheng, K. Jia, T. Bi et al., “Cosine similarity based line protection for large scale wind farms,” IEEE Transactions on Industrial Electronics, vol. 68, no. 7, pp. 5990-5999, Jul. 2021. [Baidu Scholar]
J. Duan, Z. Li, Y. Zhou et al., “Study on the voltage level sequence of future urban DC distribution network in China: a review,” International Journal of Electrical Power & Energy Systems, vol. 117, p. 105640, May 2020. [Baidu Scholar]
L. Zhang, J. Liang, W. Tang et al., “Converting AC distribution lines to DC to increase transfer capacities and DG penetration,” IEEE Transactions on Smart Grid, vol. 10, no. 2, pp. 1477-1487, Mar. 2019. [Baidu Scholar]
J. Wu, Z. Wang, L. Xue et al., “Key technologies of VSC-HVDC and its application on offshore wind farm in China,” Renewable and Sustainable Energy Reviews, vol. 36, pp. 247-255, Aug. 2014. [Baidu Scholar]
J. Li, Y. Li, L. Xiong et al., “DC fault analysis and transient average current based fault detection for radial MTDC system,” IEEE Transactions on Power Delivery, vol. 35, no. 32, pp. 1310-1320, Jun. 2020. [Baidu Scholar]
B. Li, Y. Li, and J. He, “A DC fault handling method of the MMC-based DC system,” International Journal of Electrical Power & Energy Systems, vol. 93, pp. 39-50, Dec. 2017. [Baidu Scholar]
B. Li, H. Gui, B. Li et al., “A permanent fault identification method for single-pole grounding fault of overhead transmission lines in VSC-HVDC grid based on fault line voltage,” International Journal of Electrical Power & Energy Systems, vol. 117, p. 105603, May 2020. [Baidu Scholar]
B. Li, J. He, Y. Li et al., “A novel DCCB reclosing strategy for the flexible HVDC grid,” IEEE Transactions on Power Delivery, vol. 35, no. 1, pp. 244-257, Feb. 2020. [Baidu Scholar]
B. Li, Q. Mao, J. He et al., “Adaptive reclosing strategy for the mechanical DC circuit breaker in VSC-HVDC grid,” Electric Power Systems Research, vol. 192, p. 107008, Mar. 2021. [Baidu Scholar]
X. Pei, G. Tang, and S. Zhang, “Sequential auto-reclosing strategy for hybrid HVDC breakers in VSC-based DC grids,” Journal of Modern Power Systems and Clean Energy, vol. 7, no. 3, pp. 633-643, May 2019. [Baidu Scholar]
S. Xue, J. Lian, J. Qi et al., “Fault transient characteristic and adaptive reclosing technique of MMC-HVDC network,” Power System Technology, vol. 42, no. 12, pp. 4015-4021, Dec. 2018. [Baidu Scholar]
S. Zhang, G. Zou, B. Li et al., “Fault property identification method and application for MTDC grids with hybrid DC circuit breaker,” International Journal of Electrical Power & Energy Systems, vol. 110, pp. 136-143, Sept. 2019. [Baidu Scholar]
S. Yang, X. Xiang, X. Lu et al., “An adaptive reclosing strategy for MMC-HVDC systems with hybrid DC circuit breakers,” IEEE Transactions on Power Delivery, vol. 35, no. 3, pp. 1111-1123, Jun. 2020. [Baidu Scholar]
T. Wang, G. Song, and S. T. H. Kazmi, “Adaptive single-pole auto-reclosing scheme for hybrid MMC-HVDC systems,” IEEE Transactions on Power Delivery, vol. 34, no. 6, pp. 2194-2203, Dec. 2019. [Baidu Scholar]
Z. Li, J. Duan, W. Lu et al., “Pilot acceleration line protection of flexible MVDC distribution network,” Automation of Electric Power Systems, vol. 45, no. 9, pp. 280-88, May 2021. [Baidu Scholar]
J. Duan, Z. Li, Z. Wei et al., “A line accelerated protection scheme of flexible MVDC distribution system based on transient current derivative,” Electrical Power System Research, vol. 183, p. 106269, Jun. 2020. [Baidu Scholar]
Y. Yu, Y. Jin, Q. Jiang et al., “RT-LAB based modeling and simulation analysis of flexible DC distribution network,” Power System Protection and Control, vol. 43, no. 19, pp. 125-130, Oct. 2015. [Baidu Scholar]
B. Li, J. He, Y. Li et al., “High-speed directional pilot protection for MVDC distribution systems,” International Journal of Electrical Power & Energy Systems, vol. 121, p. 106141, Oct. 2020. [Baidu Scholar]
R. Song, J. Lu, and M. Zhang, “The Shanghai practice: improve the reliability of urban MV distribution system with K-station and its new network designs,” in Proceedings of 25th International Conference on Electricity Distribution, Madrid, Spain, Jun. 2019, pp. 941-948. [Baidu Scholar]
DC Distribution Voltage, T/CEC 107-2016, 2017. [Baidu Scholar]
C. Zhang, G. Song, T. Wang et al., “Single-ended traveling wave fault location method in DC transmission line based on wave front information,” IEEE Transactions on Power Delivery, vol. 34, no. 5, pp. 2028-2038, Oct. 2019. [Baidu Scholar]
W. Xiang, S. Yang, L. Xu et al., “A transient voltage-based DC fault line protection scheme for MMC-based DC grid embedding DC breakers,” IEEE Transactions on Power Delivery, vol. 34, no. 1, pp. 334-3454, Feb. 2019. [Baidu Scholar]
B. Li, Y. Li, J. He et al., “A novel single-ended transient-voltage-based protection strategy for flexible DC grid,” IEEE Transactions on Power Delivery, vol. 34, no. 5, pp. 1925-1937, Oct. 2019. [Baidu Scholar]