Abstract:Earlier studies have reported some calculation methods for commutation failure fault level (CFFL) in line-commutated-converter based high-voltage direct current (LCC-HVDC) system under single-line-to-ground (SLG) faults. The accuracy of earlier methods is limited because they only consider the commutating voltage drop and phase shift, while neglecting the DC current variation. Hence, this paper proposes a CFFL calculation method under SLG faults considering DC current variation, for better planning and designing of LCC-HVDC systems. First, the fault commutating voltage magnitude and phase shift are calculated. Then, the fault DC voltage during different commutation processes is deduced. Based on the commutating voltage magnitude and phase shift, and DC voltage during different commutation processes under SLG faults, the characteristics of CFFL with different fault time are demonstrated and analyzed. Next, the transient time-domain response of the DC current after the fault is obtained based on the DC transmission line model. Discrete commutation processes are constructed based on the commutation voltage-time area rule to solve the extinction angle under different fault levels and fault time. Finally, the CFFL is calculated considering the fault time, commutating voltage drop, phase shift, and DC current variation. The accuracy of the proposed method compared with the traditional method is validated based on the CIGRE benchmark model in PSCAD/EMTDC.