Abstract
Modern fault-resilient microgrids (MGs) require the operation of healthy phases during unbalanced short-circuits to improve the system reliability. This study proposes a differential power based selective phase tripping scheme for MGs consisting of synchronous and inverter-interfaced distributed generators (DGs). First, the differential power is computed using the line-end superimposed voltage and current signals. Subsequently, to make the scheme threshold-free, a power coefficient index is derived and used for identifying faulted phases in an MG. The protection scheme is tested on a standard MG operating in either grid-connected or islanding mode, which is simulated using PSCAD/EMTDC. The efficacy of the scheme is also assessed on the OPAL-RT manufactured real-time digital simulation (RTDS) platform. Further, the performance of the proposed protection scheme is compared with a few existing methods. The results show that the selective tripping of faulted phases in MGs can be achieved quickly and securely using the proposed scheme.
THE generation of electric power in low- and medium-voltage distribution systems using wind and photovoltaic distributed generators (PVDGs) continues to increase progressively worldwide [
To overcome the limitations of traditional overcurrent relays, several advanced relaying schemes based on adaptive principles [
In recent years, efforts have been devoted to the fast and correct identification of fault type or phase in modern fault-resilient MGs through single- and double-pole trippings. In [
The differential energy derived from the line-end current signals through the S-transform is used in [
The aforementioned studies have reported various methods to detect and isolate faulted phases in MGs. However, in most cases, their efficacies have not been tested in grid-connected and islanding operation modes, critical fault cases (high-resistance faults and high-impedance faults (HIFs) with low-arcing currents), and non-fault switching transients (large load switching, capacitor switching, DG outage, line outage, etc.). In addition, the feasibility of the practical implementation of the most available protection schemes have not been evaluated through a real-time digital platform. Further, retraining is necessary for training-based protection schemes such as ANN and DT to cope with significant changes in system configurations, which frequently occur in MGs. Considering the above deficiencies, a fast and secure differential power based selective phase tripping scheme is proposed in this study to improve the system reliability of modern MGs.
The main contributions of this study for the effective detection and isolation of fault phases in MGs can be summarized as follows.
1) This study introduces a differential power based fault detection scheme for MGs using the measured three-phase voltage and current signals at the relay location.
2) A threshold-free power coefficient index derived from the line-end differential power is introduced to identify the fault phase in MGs.
3) The performance of the proposed protection scheme is evaluated in numerous fault and non-fault cases generated in a standard test MG system using the PSCAD/EMTDC software.
4) Based on the comparative assessment results, the proposed protection scheme outperforms those reported in some earlier studies.
5) The feasibility of the practical implementation of the proposed protection scheme is evaluated on the OPAL-RT manufactured RTDS platform.
The remainder of this paper is organized as follows. The details of the proposed protection scheme are discussed in Section II. Section III presents the results and corresponding discussions. The comparative results are presented in Section IV. Section V explicates the performance validation through the OPAL-RT manufactured RTDS platform. Finally, Section VI concludes this paper.
The voltage and current signals at the relay location change with the initiation of a fault in the power distribution network. In this study, the calculated differential power from the superimposed voltage and current signals at the relay location is utilized for fault detection. Once a fault is detected, the signs of the computed differential power of each phase at the end of a particular line are compared to identify the faulted phases. To transform the proposed scheme into a threshold-free FPI one, instead of directly utilizing the differential power, a power coefficient index is derived for each phase. The computation steps of the proposed protection scheme are as follows.
The work flow and practical implementation of the proposed protection scheme are shown in

Fig. 1 Work flow of proposed protection scheme.
The measured voltage and current signals at relay R12 are sampled at 1 kHz, which are denoted as , , for voltage signals and , , for current signals at the instant, respectively. The one-cycle differences of the voltage and current signals extracted at the instant at relay R12 are calculated using (1) and (2), respectively.
(1) |
(2) |
where is the number of samples in one cycle. Similarly, the one-cycle difference of the voltage and current signals can be extracted at relay R21 using (1) and (2). The three-phase voltages and currents at relay R21 at the instant are denoted as , , and , , , respectively. The corresponding one-cycle differences are denoted as , , and , , , respectively.
The one-cycle differences of voltage and current signals (superimposed components) are conventionally used to detect and classify faults in power transmission and distribution networks [
(3) |
(4) |
Once the differential power magnitudes of the three phases at relays R12 and R21 are computed, the magnitudes of the three-phase differential power, and , at relays R12 and R21 can be calculated using (5) and (6), respectively.
(5) |
(6) |
In this study, and are used as the criteria for the detection of faults in MGs.
Relays R12 and R21 detect a fault if (7) and (8) are satisfied, respectively.
(7) |
(8) |
where is the threshold.
Ideally, the magnitudes of the differential power calculated at relays R12 and R21 are zero during the normal operation of the power system. When a fault initiates, the magnitude of the differential power calculated at the relay location increases. Thus, the computed differential power at the relay location can be used as a feature for fault detection. However, during the initiation of non-fault transients, a certain magnitude of differential power exists, which may be misinterpreted as a fault. Thus, a threshold of is considered to avoid false fault detection during different non-fault transients. Based on the simulated results, the chosen threshold can ensure the reliable fault detection in MGs.
Once a fault is detected, the next task is the FPI. At the relay position, the phasor relationships between the estimated superimposed voltage and current signals of a particular phase during forward and reverse faults are shown in

Fig. 2 Relationship between superimposed voltage and current signals extracted during forward and reverse faults. (a) Forward fault. (b) Reverse fault.
Ideally, the calculated line-end differential power of each phase is zero during the normal operation, and after an internal fault occurs, the differential power across the faulted phase becomes negative. However, the simulation study indicates that even during non-fault transients, the differential power values calculated at the line-end phases become negative and have a small magnitude. Thus, for secure discrimination of faults from transients, a suitable threshold is essential. It is further observed that the selection of a suitable threshold for discriminating critical faults (e.g., HIFs) from non-fault transients may become exigent. Moreover, the integration of MGs into distribution systems through power electronic converters affects the voltage and current signals of non-fault phases. In such situations, the proper threshold selection becomes difficult. To solve this problem and make the proposed FPI task threshold-free, the power coefficients of individual phases at the line end are calculated; the power coefficient is simply a representation of the differential power per unit. The steps involved in calculating the power coefficients of each phase at the line end and the proposed FPI rules are expressed as:
(9) |
(10) |
where , and , are the power coefficients of the three phases calculated at relays R12 and R21, respectively.
If (11)-(13) are satisfied, respectively, phases a, b, c will be detected as the fault phase, respectively.
(11) |
(12) |
(13) |
Otherwise, the condition is normal.
In
The system shown in
An AG fault (fault resistance ) is set in line 1-2 at 2.2 s with 4 km from relay R12 (

Fig. 3 Performance results at relays R12 and R21 during AG fault in line 1-2. (a) Current. (b) Voltage. (c) Differential power . (d) Power coefficient (e) Output.
The results of the adjacent non-fault line 2-3, as shown in

Fig. 4 Performance results at relays R23 and R32 during AG fault in line 1-2. (a) Current. (b) Voltage. (c) Differential power . (d) Power coefficient (e) Output.
An AC fault is set in line 2-3 at 2.3 s with 5 km from relay R23 (

Fig. 5 Performance results at relays R23 and R32 during AC fault in line 2-3. (a) Current. (b) Voltage. (c) Differential power . (d) Power coefficient . (e) Output.
Further, an ABG fault () is set in line 2-3 at with 3 km from relay R23. The results in

Fig. 6 Performance results at relays R23 and R32 during ABG fault in line 2-3. (a) Current. (b) Voltage. (c) Differential power (d) Power coefficient (e) Output.
A high-resistance BG fault () is set in line 1-2 at with from relay R12 (

Fig. 7 Performance results at relays R12 and R21 during high-resistance BG fault in line 1-2. (a) Current. (b) Voltage. (c) Differential power . (d) Power coefficient . (e) Output.
In electric power distribution systems, energized conductors usually meet poorly grounded objects such as trees, wood fences, and vehicles. Sometimes, the overhead conductors break and touch high-impedance ground surfaces such as asphalt, concrete, grass, and sand. These contacts restrict the fault current from a few milliamperes to only [
Thus, it is necessary to correctly detect HIFs in electric power distribution networks. However, HIF detection becomes more difficult with the increasing penetration of renewable energy based DGs into the distribution networks [
The HIF currents are associated with electric arcs and hence are random, non-linear, asymmetric, and intermittent. The circuit model considered in this study, exhibiting the above characteristics of the HIF current, is similar to that in [

Fig. 8 Schematic diagram of HIF model.

Fig. 9 Typical voltage and current waveforms during HIF. (a) Voltage. (b) Current.

Fig. 10 Performance results at relays R12 and R21 during HIF (AG type) in line 1-2. (a) Current. (b) Differential power . (c) Power coefficient . (d) Output.
A CG fault ( ) is created in line 1-4 at 3.2 s with 7 km from relay R14 (

Fig. 11 Performance results at relays R14 and R41 during CG fault in line 1-4. (a) Current. (b) Voltage. (c) Differential power . (c) Power coefficient . (e) Output.
A BCG fault () is initiated in line 1-4 at with from relay R14 (

Fig. 12 Performance results at relays R14 and R41 during BCG fault in line 1-4. (a) Current. (b) Voltage. (c) Differential power . (c) Power coefficient . (e) Output.
In the islanding mode, an AG fault () is initiated in line 2-3 at with from relay R23 (

Fig. 13 Performance results at relays R23 and R32 during AG fault in line 2-3. (a) Current. (b) Voltage. (c) Differential power . (c) Power coefficient . (e) Output.
Distribution networks sometimes operate with unbalanced loads. In the islanding mode, let phase c of load L5 be disconnected, which results in an unbalanced condition in the system. During this period, a BG fault () is initiated in line 4-5 at with 6 km from relay R45 (

Fig. 14 Performance results at relays R45 and R54 during BG fault with unbalanced load in line 4-5. (a) Current. (b) Voltage. (c) Differential power . (c) Power coefficient . (e) Output.
In the islanding mode, an ABG fault () is initiated in line 1-2 at with from relay R12 (

Fig. 15 Performance results at relays R12 and R21 during ABG fault in line 1-2. (a) Current. (b) Voltage. (c) Differential power . (c) Power coefficient . (e) Output.
For security assessment, the proposed protection scheme is tested on different possible switching events such as large load switching, capacitor switching, sudden DG outages, line outages, and presence of noise in the current signal. The corresponding results of some non-fault transient cases are considered below.
At 3.5 s, load L2 at Bus-1 suddenly increases to 1.4 times the rated value (

Fig. 16 Performance results at relays R12 and R21 during load switching at Bus-1. (a) Current. (b) Voltage. (c) Differential power . (c) Power coefficient . (e) Output.
A 1.5 kvar capacitor connected to Bus-1 (

Fig. 17 Performance results at relays R23 and R32 during capacitor switching at Bus-1. (a) Current. (b) Voltage. (c) Differential power . (c) Power coefficient . (e) Output.
As shown in
The PVDG is suddenly disconnected at 2.1 s from the utility grid (

Fig. 18 Performance results at relays R14 and R41 during sudden outage of PVDG at Bus-4. (a) Current. (b) Voltage. (c) Differential power . (c) Power coefficient . (e) Output.
The proposed relay scheme is compared with three recent relay schemes proposed for MG protection, namely S-transform operated differential energy scheme [
The comparative results of a high-resistance CG fault () initiated at with from relay R14 in line 1-4 (

Fig. 19 Comparative assessment results during high-resistance CG fault in line 1-4. (a) Currents measured at relays R14 and R41. (b) S-transform operated differential energy scheme. (c) Cross-alienation coefficient method. (d) Active power of zero- or d-frame component consumed by fault resistance . (e) Differential power . (f) Power coefficient . (g) Output.
As shown in
The comparative results of an HIF (AG type) in line 1-2 with 8 km from relay R12 (

Fig. 20 Comparative assessment results during HIF (AG type) in line 1-2. (a) Currents measured at relays R12 and R21. (b) S-transform operated differential energy scheme. (c) Cross-alienation coefficient scheme. (d) Active power of zero- or d-frame component consumed by fault resistance Rf0. (e) Differential power . (f) Power coefficient . (g) Output.
The HIF model shown in
The comparative results of these two fault modes confirm that the proposed scheme can detect even the critical faults in MGs and isolate them more quickly and securely than others. Thus, the proposed relay scheme outperforms those reported in some earlier studies in detecting and isolating fault phases in MGs.
To evaluate the effectiveness and correctness of the proposed selective phase tripping scheme in a real network, it is implemented and validated through the OPAL-RT manufactured (OP4510) RTDS platform. The hardware setup for the real-time simulation study is shown in Supplement Materials. For simplification, the result of only one fault case is presented.
An AG fault () is initiated in line 1-2 at with 7 km from relay R12 (

Fig. 21 RTDS results at relays R12 and R21 during AG fault in line 1-2 in grid-connected mode. (a) Current. (b) Voltage. (c) Output.
In this study, a differential power coefficient based threshold-free and computationally efficient protection scheme is proposed for the selective tripping of fault phases in modern MGs consisting of PVDGs and SDGs. The performance of the proposed protection scheme is validated on numerous faults, including critical faults (high-resistance faults and HIFs with low-arcing currents) and non-fault transients (large load switching, capacitor switching, DG outage, line outage, etc.) simulated in a standard MG operating in both grid-connected and islanding modes. The results indicate that through the proposed protection scheme, fault phases, including critical faults in MGs, can be detected and isolated within (half a cycle of the power frequency signal). In addition, the scheme is immune to switching transients. Comparative assessment results also clearly show that the proposed protection scheme outperforms the available protection techniques, especially in the detection and isolation of critical faults such as high-resistance faults and low-current arcing HIFs in MGs. Further, the RTDS results through OPAL-RT (OP4510) prove the feasibility of the proposed protection scheme for its practical implementation as MG protection.
References
S. Parhizi, H. Lotfi, A. Khodaei et al., “State of the art in research on microgrids: a review,” IEEE Access, vol. 3, pp. 890-925, Jun. 2015. [Baidu Scholar]
R. F. Arritt and R.C. Dugan, “Distribution system analysis and the future smart grid,” IEEE Transactions on Industrial Applications, vol. 47, no. 6, pp. 2343-2350, Sept. 2011. [Baidu Scholar]
A. Girgis and S. Brahma, “Effect of distributed generation on protective device coordination in distribution system,” in Proceedings of International Conference Power Engineering in Large Engineering Systems, Halifax, Canada, Jul. 2001, pp. 115-119. [Baidu Scholar]
L. V. Strezoski, N. R. Vojnovic, V. C. Strezoski et al., “Modeling challenges and potential solutions for integration of emerging DERs in DMS applications: power flow and short-circuit analysis,” Journal of Modern Power Systems and Clean Energy, vol. 7, no. 6, pp. 1365-1384, Nov. 2019. [Baidu Scholar]
T. K. Abdel-Galil, A. E. Abu-Elanien, E. F. El-Saadany et al., “Protection coordination planning with distributed generation,” Qualsys Engineering Company Incorporated, vol. 149, pp. 98-107, Jun. 2007. [Baidu Scholar]
S. A. Gopalan, V. Sreeram, and H. H. C. Iu, “A review of coordination strategies and protection schemes for microgrids,” Renewable and Sustainable Energy Review, vol. 32, pp. 222-228. Mar. 2014. [Baidu Scholar]
P. Mahat, Z. Chen, B. Bak-Jensen et al., “A simple adaptive overcurrent protection of distribution systems with distributed generation,” IEEE Transactions on Smart Grid, vol. 2, no. 3, pp. 428-437, Jun. 2011. [Baidu Scholar]
A. Oudalov and A. Fidigatti, “Adaptive network protection in microgrids,” International Journal of Distribution Energy Resources, vol. 5, no. 3, pp. 201-226, Sept. 2009. [Baidu Scholar]
M. S. Elbana, N. Abbasy, A. Meghed et al., “µPMU-based smart adaptive protection scheme for microgrids,” Journal of Modern Power Systems and Clean Energy, vol. 7, no. 4, pp. 887-898, Jun. 2019. [Baidu Scholar]
E. Sortomme, S. S. Venkata, and J. Mitra, “Microgrid protection using communication-assisted digital relays,” IEEE Transactions on Power Delivery, vol. 25, no. 4, pp. 2789-2796, Oct. 2009. [Baidu Scholar]
T. S. Ustun, C. Ozansoy, and A. Zayegh, “Modeling of a centralized microgrid protection system and distributed energy resources according to IEC 61850-7-420,” IEEE Transactions on Power Systems, vol. 27, no. 3, pp. 1560-1567, Feb. 2012. [Baidu Scholar]
J. R. Agüero, J. Wang, and J. J. Burke, “Improving the reliability of power distribution systems through single-phase tripping,” in Proceedings of IEEE PES Transmission and Distribution Conference and Exposition, New Orleans, USA, Apr. 2010, pp. 1-7. [Baidu Scholar]
Q. Li, Z. Xu, and L. Yang, “Recent advancements on the development of microgrids,” Journal of Modern Power Systems and Clean Energy, vol. 2, no. 3, pp. 206-211, Sept. 2014. [Baidu Scholar]
A. M. El-Zonkoly, “Fault diagnosis in distribution networks with distributed generation,” Electric Power Systems Research, vol. 81, no. 7, pp. 1482-1490, Jul. 2011. [Baidu Scholar]
M. Dewadasa, A. Ghosh, G. Ledwich et al., “Fault isolation in distributed generation connected distribution networks,” IET Generation, Transmission & Distribution, vol. 5, no. 10, pp. 1053-1061, Oct. 2011. [Baidu Scholar]
A. Hooshyar, E. F. El-Saadany, and M. Sanaye-Pasand, “Fault type classification in microgrids including photovoltaic DGs,” IEEE Transactions on Smart Grid, vol. 7, no. 5, pp. 2218-2229, Sept. 2015. [Baidu Scholar]
M. M. Mahfouz and M. A. El-Sayed, “Smart grid fault detection and classification with multi-distributed generation based on current signals approach,” IET Generation, Transmission & Distribution, vol. 10, no. 16, pp. 4040-4047, Dec. 2016. [Baidu Scholar]
O. Dharmapandit, R. K. Patnaik, and P. K. Dash, “Detection, classification, and location of faults on grid‐connected and islanded AC microgrid,” International Transactions on Electrical Energy Systems, vol. 27, no. 12, pp. 1-33, Dec. 2017. [Baidu Scholar]
E. Casagrande, W. L. Woon, H. H. Zeineldin et al., “A differential sequence component protection scheme for microgrids with inverter-based distributed generators,” IEEE Transactions on Smart Grid, vol. 5, no. 1, pp. 29-37, Jan. 2014. [Baidu Scholar]
S. Kar and S. R. Samantaray, “Time-frequency transform-based differential scheme for microgrid protection,” IET Generation, Transmission & Distribution, vol. 8, no. 2, pp. 310-320, Feb. 2014. [Baidu Scholar]
X. Liu, Z. Xie, Q. Sun et al., “A novel protection scheme against fault resistance for AC microgrid,” Mathematical Problems in Engineering, vol. 2017, pp. 1-11, Feb. 2017. [Baidu Scholar]
H. Lala, S. Karmakar, and S. Ganguly, “Detection and localization of faults in smart hybrid distributed generation systems: a Stockwell transform and artificial neural network‐based approach,” International Transactions on Electrical Energy Systems, vol. 29, no. 2, pp. 1-18, Feb. 2019. [Baidu Scholar]
S. Kar, S. R. Samantaray, and M. D. Zadeh, “Data-mining model based intelligent differential microgrid protection scheme,” IEEE Systems Journal, vol. 11, no. 2, pp. 1161-1169, Jan. 2015. [Baidu Scholar]
D. P. Mishra, S. R. Samantaray, and G. Joos, “A combined wavelet and data-mining based intelligent protection scheme for microgrid,” IEEE Transactions on Smart Grid, vol. 7, no.5, pp. 2295-2303, Oct. 2016. [Baidu Scholar]
M. Dehghani, M. H. Khooban, and T. Niknam, “Fast fault detection and classification based on a combination of wavelet singular entropy theory and fuzzy logic in distribution lines in the presence of distributed generations,” International Journal of Electrical Power and Energy Systems, vol. 78, pp. 455-462, Jun. 2016. [Baidu Scholar]
M. Mishra and R. K. Rout, “Detection and classification of micro-grid faults based on HHT and machine learning techniques,” IET Generation, Transmission & Distribution, vol. 12, no.2, pp. 388-397. Sept. 2017. [Baidu Scholar]
S. Mirsaeidi, D. M. Said, M. W. Mustafa et al., “A protection strategy for micro-grids based on positive-sequence component,” IET Renewable Power Generation, vol. 9, no. 6, pp. 600-609, Mar. 2015. [Baidu Scholar]
A. P. Apostolov, D. Tholomier, and S. H. Richards, “Superimposed components based sub-cycle protection of transmission lines,” in Proceedings of IEEE PES Power System Conference and Exposition, New York, USA, Oct. 2004, pp. 592-597. [Baidu Scholar]
G. Benmouyal and J. Roberts, “Superimposed quantities: their true nature and application in relays,” in Proceedings of the 26th Annual Western Protection Relay Conference, Spokane, USA, Oct. 1999, pp. 1-18. [Baidu Scholar]
E. Sedoyeka, Z. Hunaiti, M. A. Nabhan et al., “WiMAX mesh networks for underserved areas,” in Proceedings of International Conference on Computer System Applications, Doha, Qatar, Mar. 2008, pp. 1070-1075. [Baidu Scholar]
T. S. Basso and R. DeBlasio, “IEEE 1547 series of standards: interconnection issues,” IEEE Transactions on Power Electronics, vol. 19, no. 5, pp. 1159-1162, Sept. 2004. [Baidu Scholar]
K. Sarwagya, S. De, and P. K. Nayak, “High-impedance fault detection in electrical power distribution systems using moving sum approach,” IET Science Measurement and Technology, vol. 12, no. 1, pp. 1-8, Aug. 2017. [Baidu Scholar]
A. Ghaderi, H. A. Mohammadpour, H. L. Ginn et al., “High-impedance fault detection in the distribution network using the time-frequency-based algorithm,” IEEE Transactions on Power Delivery, vol. 30, no. 3, pp. 1260-1268. Jun. 2015. [Baidu Scholar]