Abstract
Wind-thermal-bundled system has emerged as the predominant type of power system, incorporating a significant proportion of renewable energy. The dynamic interaction mechanism of the system is complex, and the issue of oscillation stability is significant. In this paper, the damping characteristics of the direct current (DC) capacitance oscillation mode are analyzed using the path analysis method (PAM). This method combines the transfer-function block diagram with the damping torque analysis (DTA). Firstly, the linear models of the permanent magnet synchronous generator (PMSG), the synchronous generator (SG), and the alternating current (AC) grid are established based on the transfer functions. The closed-loop transfer-function block diagram of the wind-thermal-bundled systems is derived. Secondly, the block diagram reveals the damping path and the dynamic interaction mechanism of the system. According to the superposition principle, the transfer-function block diagram is reconstructed to achieve the damping separation. The damping coefficient of the DTA is used to quantify the effect of the interaction between the subsystems on the damping characteristics of the oscillation mode. Then, the eigenvalue analysis is used to analyze the system stability. Finally, the damping characteristic analysis is validated by time-domain simulations.
IN China, wind farms are mainly concentrated in the western, northern, and eastern coastal areas. The wind power and thermal power are transmitted to central load centers through high-capacity, long-distance transmission systems [
Currently, several methods are available to study system oscillations, including the eigenvalue method, impedance model analysis (IMA) method, open-loop mode resonance method, damping torque analysis (DTA) method, and time-domain simulation method [
1) The eigenvalue method based on the small-signal model is used to analyze the variables and subsystems related to the oscillation modes. Using the eigenvalue method, it has been found that PMSGs connected to the power system could reduce the system stability under small disturbances [
2) The IMA method is a frequency domain method that explains the interaction mechanism between subsystems based on their external impedance characteristics. The effect of the PMSGs on the sub-synchronous torsional interactions (SSTI) of thermal power units is investigated by IMA, taking into account the field winding and damper winding of synchronous machines. It is shown that PMSGs can lead to insufficient damping of SSTI [
3) The open-loop-mode resonance analysis method has investigated the mechanism of strong interaction by studying the open-loop-mode coupling. It is found that the simultaneous involvement of the PMSG and synchronous generator (SG) in oscillation modes is due to the proximity of the converter oscillation mode (COM) and the electromechanical oscillation mode (EOM) [
4) In the DTA method, the studied system is equated to be second-order due to the similarity between the system and the rotor motion equation of the SG. The damping torque coefficient is used to study the vibration characteristics of the system. In [
However, the eigenvalue analysis and open-loop mode resonance analysis methods suffer from the “dimensional disaster” problem and are unable to analyze the transmission path of frequency disturbances. IMA can explain the vibration mechanism at the physical level and can be used to model the “black (gray) box” system. However, it is difficult to uncover the dynamic interactions within the system from the external impedance characteristics of the device alone. The DTA method can only study the damping characteristics of the system itself and cannot separate the dynamics of the interactions between the various links in the system. The differential algebraic equation (DAE) is used to describe the system dynamics in time-domain simulation methods, but it cannot reveal the oscillation coupling mechanism. Time-domain simulation method can be used to verify the validity of the theoretical analysis. Given the limitations of the above methods, it is crucial to explore the dynamic interaction mechanism from a new perspective.
The DTA [
In this paper, the path analysis method (PAM) is used to analyze the stability of the DC capacitance oscillation mode by combining the transfer-function block diagram and DTA. Compared with other methods, PAM can elucidate the path of disturbance transmission and the coupling relationships between the subsystems. The effect of the interaction between the subsystems on the damping of the oscillation modes is quantified by the damping reconstruction. The contributions of this paper include the following aspects.
1) The linear models (LMs) of the PMSG, SG, and AC grid are established using the transfer function equations, and the closed-loop transfer-function block diagram of the wind-thermal-bundled system is derived.
2) The closed-loop transfer-function block diagram shows the damping path and the dynamic interaction process of the subsystem. The block diagram is reconstructed to achieve damping separation based on the superposition principle. The DTA method is used to quantify the effect of dynamic interaction between subsystems on the DC capacitance oscillation mode.
3) The effect of system parameters on the damping of the DC capacitance oscillation mode is analyzed using the damping separation method and the eigenvalue method, and verified by time-domain simulation.
The remainder of this paper is organized as follows. In Section II, the LM for the wind-thermal-bundled system is established, and the transfer-function block diagram is obtained. Sections III and IV conduct damping characteristic analyses based on PAM and eigenvalue analysis method, respectively. Section III shows the coupling relationships between the subsystems based on the block diagram, which is constructed to achieve damping separation. In Section IV, the state-space model of the wind-thermal-bundled system is established, and the oscillation mode of the system is analyzed with varying parameters. In Section V, the effect of the system parameters on the damping of the DC capacitance oscillation mode is confirmed by simulation results. Conclusions are given in Section VI.
In this section, the transfer function equations are used to establish the LMs of the PMSG, SG, and AC grid. Then, the transfer-function block diagram of the wind-thermal-bundled system is derived, and its validity is verified by the step response characteristics of the electromagnetic transient model (ETM). The diagram of the wind-thermal-bundled system is shown in

Fig. 1 Diagram of wind-thermal-bundled system.
In the following, the voltage ur is used as an example, and , , .
The PMSG subsystem consists of the DC capacitance, the GSC, the PLL, the filter inductance, and the grid-connected transmission lines. The control diagram of the GSC is shown in

Fig. 2 Control diagram of GSC.
In
The dynamics of the constant DC voltage outer loop control for the GSC are given as:
(1) |
where .
The bandwidth of the DC voltage outer loop is designed to be one-tenth of the bandwidth of the current inner loop. Therefore, the grid-side current can follow its reference value based on the current inner loop. It can be expressed as and . As the power factor of the GSC is 1, is set to be 0. Then, both and igq are equal to 0. So, the output active power of the GSC is:
(2) |
where G1 is the transfer function matrix from and to . The expression for G1 is given in (A1) in Appendix A.
The dynamic equation for the DC capacitance is:
(3) |
The dynamic equation for the PLL is:
(4) |
The filter line dynamics are:
(5) |
In (5), can be written as:
(6) |
where is the transfer function matrix from and to . The expression for is given in (A2) in Appendix A.
The dynamic equations for the capacitance and impedance of the lines connected with the network are given as:
(7) |
(8) |
where and are the transfer function matrices from and to , respectively; and are the transfer function matrices from and to , respectively; and the expressions for - are given in (A3) and (A4) in Appendix A.
For ug and ig, the transformation equations between the x-y frame and the d-q frame are:
(9) |
(10) |
where Tug is the transfer function matrix from and to ; and Tig is the transfer function matrix from and to . The detailed expressions of Tug and Tig are given in (A5) and (A6) in Appendix A.
Combining (7), (8), and (10) yields :
(11) |
where is the transfer function matrix from , , to . As is complicated, it will not be listed in this paper.
Combining (7), (9), and (10), we can obtain as:
(12) |
where is the transfer function matrix from , , to .
Based on (1)-(4), (6), (11), and (12), the LM of the PMSG is shown in

Fig. 3 LM of PMSG.
The voltage equation for SG is given as:
(13) |
The third-order dynamic model of SG is given as:
(14) |
Considering the governor and turbine of SG, the relationship between the and is:
(15) |
In the d2-q2 frame, the dynamic equation of the SG grid-connected transmission line is:
(16) |
Combining (13) and (16), we can obtain:
(17) |
Substituting (13) and (17) into the third formula of (14), we can obtain:
(18) |
where is the transfer function matrix from to , and the detailed expression of is given in (A7) in Appendix A.
By substituting (18) into (16), can be written as:
(19) |
where is the transfer function from to , and the detailed expression of is given in (A8) in Appendix A.
The active power of SG is:
(20) |
By substituting (16) and (19) into (20), is obtained as:
(21) |
where is the transfer function matrix from to .
For and , the conversion relation between the d2-q2 frame and the x-y frame is given as:
(22) |
(23) |
where G12 is the transfer function matrices from and to ; and G13 is the transfer function matrices from and to . The detailed expressions of G12 and G13 are given in (A9) and (A10) in Appendix A, respectively.
Based on (14), (19), (21)-(23), the LM of SG is shown in

Fig. 4 LM of SG.
The dynamics of the AC grid are given as:
(24) |
where and are the transfer function matrices from and to , respectively. The expressions of and are given in (A11) in Appendix A.
Omitting the change of , (24) can be rewritten as:
(25) |
According to
(26) |
The combination of (25) and (26) gives:
(27) |
where is the transfer function matrix from and to . The detailed expression of is given in (A12) in Appendix A.
Based on (27), the aggregated LM of the AC grid is shown in

Fig. 5 Aggregated LM of AC grid.
By combining (2), (3), (5), (11), and (12) to eliminate the intermediate variables , , , and , the output power of the PMSG is calculated as:
(28) |
where is the transfer function from to ; and is the transfer function matrix from to .
By combining (1), (4), (11), and (12) to eliminate the intermediate variables and , can be rewritten as:
(29) |
where and are the transfer function matrices from and to , respectively.
Based on (3), (28), and (29), the aggregated LM of the PMSG is shown in

Fig. 6 Aggregated LM of PMSG.
By substituting (22) into (21), the active power of SG is obtained as:
(30) |
where is the transfer function from to ; and is the transfer function matrix from to . The detailed expressions of and are given in (A13) in Appendix A.
Combining (19), (22), and (23), we can obtain:
(31) |
where and are the transfer function matrices from and to , respectively. The expressions of and are given in (A14) and (A15) in Appendix A, respectively.
Substituting (15) into (14), we obtain the transfer function from to :
(32) |
Based on (14) and (30)-(32), the aggregated LM of SG is shown in

Fig. 7 Aggregated LM of SG.
According to (3), (14), and (27)-(32), the transfer-function block diagram of the wind-thermal-bundled system is shown in

Fig. 8 Transfer-function block diagram of wind-thermal-bundled system.
From the above derivation, it is clear that the transfer-function block diagram of the system before and after the polymerization corresponds to each other, and the dynamic interaction analysis can be performed based on the transfer-function block diagram.
Before analyzing the dynamic interaction mechanism, the accuracy of the LM in MATLAB should be validated using the ETM in DIgSILENT/PowerFactory. The reference DC voltage Udcref has a step change from 1.1 p.u. to 1.05 p.u. at s, and the response curves of the system under LM and ETM are shown in

Fig. 9 Response curves following a change of Udcref from 1.1 p.u. to 1.05 p.u.. (a) Pt of SG. (b) Io of SG. (c) Pe of GSC. (d) Udc of PMSG.
In this section, the analysis of the damping path is presented based on the transfer-function block diagram. The block diagram is reconstructed to isolate the interaction damping. The factors influencing the damping characteristics are studied based on the damping reconstruction.
The block diagram of the damping path analysis, as shown in

Fig. 10 Block diagram of damping path analysis.
Damping path 1 can be described as the path through which the disturbance is transmitted from to , assuming that remains constant.
Damping path 1 consists of the transfer functions and . This indicates that path 1 is related to the DC capacitance of the PMSG and the outer loop control of the GSC. Damping path 1 is referred to as the internal oscillation transfer path of the PMSG.
Damping path 2 can be described as follows. When changes, the disturbance is transmitted from to , then from to , and finally from to . Damping path 2 passes through three subsystems: PMSG, SG, and AC grid, and includes two closed-loop paths denoted as a and b, which are indicated by oval dashed lines. The closed-loop path a passes through and , and consists of the transfer function matrices and , which represent the interaction between the PMSG and the AC grid. The closed loop path b passes through and and consists of the transfer function matrices and , reflecting the interaction between the AC system and the SG. The closed loops a and b interact at the PCC voltage to form a closed crossed loop. When the voltage is disturbed, the currents and change due to the existence of closed loops a and b, which in turn affect the dynamics of . Thus, damping path 2 is referred to as the oscillation coupling path among the PMSG, SG, and AC grid.
Furthermore, the interaction processes can be divided into two groups: the controller interaction in the PMSG, and the interaction among the PMSG, SG, and AC grid. The controller interaction in the PMSG can be understood as the dynamic process of controller interaction in the PMSG system, which is caused by disturbances through a closed loop (damping path 1). The interaction between the PMSG, the SG, and the AC grid can be understood as the dynamic interplay between the subsystems triggered by voltage and current disturbances at the PCC driven by the closed loop (damping path 2).
According to the superposition principle of linear systems, the transfer function block diagram is reconstructed, and the damping provided by the dynamic interaction is quantified. The damping separation procedure is as follows.
Step 1: based on (14) and (30), we can obtain (33) and

Fig. 11 Damping reconstruction process. (a) Step 1. (b) Step 2. (c) Step 3. (d) Step 4.
(33) |
where is the transfer function matrix from to . The expression of is given in (A16) in Appendix A.
Step 2: combining (28) and (21), we obtain (34) and
(34) |
where is the transfer function matrix from to . The expression of is given in (A17) in Appendix A.
Step 3: combining (27), (29), and (34), we obtain (35) and
(35) |
where is the transfer function matrix from to .
The open-loop transfer function matrix represents the interaction between the PMSG and the SG and the interaction between the PMSG and the AC system. If , i.e., the SG is not connected to the system and the interaction between the PMSG and the SG is not considered, the block diagram is simplified. The corresponding open loop transfer function matrix is obtained by substituting (29) into (27). represents the interaction between the PMSG and the AC grid. According to the superposition principle of linear systems, is subtracted from to obtain , where represents the interaction between the PMSG and the SG. The expressions for , , and are given in (36), and the transfer function block diagram is shown in
(36) |
Step 4: when is selected as the input variable and Udc is selected as the output variable, three transfer functions from Udc to the variables Pe-Pin and Pe are obtained using the damping separation method, as shown in
(37) |
where is the internal damping of the PMSG; is the damping of the DC capacitance oscillation influenced by the interaction between the PMSG and the AC grid; and is the damping influenced by the interaction between the PMSG and the SG system.
The corresponding damping coefficient can be calculated from:
(38) |
where Z1 is the PMSG self-damping coefficient; Z21 is the PMSG-grid interaction damping coefficient; Z22 is the PMSG-SG interaction damping coefficient; and Z2 is the interaction damping coefficient. The total damping coefficient of the system is .
To study the influence of the proportional coefficient of DC voltage outer loop of GSC control Kpdc on the damping coefficient,

Fig. 12 Damping characteristic analysis with change of Kpdc. (a) Frequency characteristic curves of Z21 and Z22. (b) Frequency characteristic curves of Z1, Z2, and Z.
As shown in
To study the influence of the integral coefficient of DC voltage outer loop of GSC control Kidc on the damping coefficient,

Fig. 13 Damping characteristic analysis with change of Kidc. (a) Frequency characteristic curves of Z21 and Z22. (b) Frequency characteristic curves of Z1, Z2, and Z.
As shown in
To study the influence of short-circuit ratio (SCR) on the damping coefficient,

Fig. 14 Damping characteristic analysis with change of SCR. (a) Frequency characteristic curves of Z21 and Z22. (b) Frequency characteristic curves of Z1, Z2, and Z.
As shown in
To study the influence of the time constant of the hydraulic motor T1 on the damping coefficient,

Fig. 15 Damping characteristic analysis with change of T1. (a) Frequency characteristic curves of Z21 and Z22. (b) Frequency characteristic curves of Z1, Z2, and Z.
As shown in
The small-signal models for PMSG and SG have been extensively studied, e.g., [
(39) |
Based on (37) and the parameters in Appendix B Table BI, the primary oscillation modes of the wind-thermal-bundled system are shown in
Oscillation mode | Eigenvalue | Oscillation frequency (Hz) | Damping ratio |
---|---|---|---|
λ1,2 | 2.53 | 0.2063 | |
λ3,4 | 8.51 | -0.3621 | |
λ5,6 | 14.43 | 0.1150 | |
λ7,8 | 51.11 | 0.0392 | |
λ9,10 | 56.75 | 0.0631 | |
λ11,12 | 286.39 | 0.0369 |
As shown in
The normalized PFs of the oscillation modes have been calculated, and it has been shown that the oscillation mode 3,4 is associated with the DC voltage control of the GSC. The effect of the system parameters on the mode 3,4 is studied.

Fig. 16 Variation of oscillation mode λ3,4 and damping ratio with different Kpdc. (a) Oscillation mode. (b) Damping ratio.
As shown in

Fig. 17 Variation of oscillation mode λ3,4 and damping ratio with different Kidc. (a) Oscillation mode. (b) Damping ratio.
In this section, the wind-thermal-bundled system is constructed in DIgSILENT. At s, Kidc is changed from 133 to 1000 to excite SSO. Other parameters are in accordance with Appendix B Table BI. The DC capacitance voltage curves with different parameters are shown to validate the above analysis. When the system is disturbed, the DC voltage curves with different Kpdc, Kidc, SCR, and T1 are shown in

Fig. 18 DC voltage response curves with different parameters. (a) Kpdc. (b) Kidc. (c) SCR. (d) T1.
In
The damping characteristics of the wind-thermal-bundled system are analyzed using the PAM. The conclusions are given as follows.
1) The LMs for the PMSG, SG, and AC grid are established, respectively, and the LMs of the subsystems are connected to construct the transfer-function block diagram of the system.
2) The damping path analysis is presented based on the transfer-function block diagram. The interaction mechanism between the subsystems can be interpreted as a dynamic process driven by voltage disturbances and current disturbances at the PCC.
3) Based on the damping separation, the total damping of the DC capacitance-dominated oscillation mode can be divided into three parts: PMSG internal damping coefficient, PMSG-SG interaction damping coefficient, and PMSG-grid interaction damping coefficient.
4) The effect of the parameters on the damping characteristics is analyzed using the damping separation method and the eigenvalue analysis method, respectively. The analysis shows that Kpdc and SCR have a positive effect on the damping of the DC capacitance-dominated oscillation mode, while Kidc and T1 have a negative effect. The analysis results are of great importance for practical engineering.
NOMENCLATURE
Symbol | —— | Definition |
---|---|---|
A. | —— | Variables |
—— | Grid frequency | |
—— | Rated frequency | |
—— | Power angle and frequency of synchronous generator (SG) | |
—— | Phase locked loop (PLL) output angle | |
—— | State variable matrix | |
—— | Input variable matrix | |
A | —— | Coefficient matrix |
B | —— | Input matrix |
C1 | —— | Line capacitance |
Cdc | —— | Direct current (DC) capacitance between machine-side converter (MSC) and grid-side converter (GSC) |
Efd | —— | Forced no-load electromotive force of SG |
—— | q-aixs transient electromotive force of SG | |
FHP | —— | Power proportional coefficient of high-pressure cylinder |
HPLL(s) | —— | Transfer function from to |
Kδ | —— | Reciprocal of unequal rate |
Kp | —— | Proportional coefficient of proportional-integral-derivative (PID) link in governor system |
Kpdc, Kidc | —— | Proportional and integral coefficients of constant DC voltage control |
kpPLL, kiPLL | —— | Proportional coefficient and integral coefficient of PLL |
M, D | —— | Inertia and damping coefficients of SG |
Pe | —— | Input power of GSC |
Pin | —— | Output active power of MSC |
Pm, Pt | —— | Mechanical power and electromagnetic power of SG |
R1, L1, i1 | —— | Grid-side resistance, inductance, and current of permanent magnet synchronous generator (PMSG) |
R2, L2 | —— | Equivalent resistance and inductance of alternating current (AC) grid |
Rg, Lg | —— | Filter resistance and inductance of PMSG |
Ro, Lo | —— | Resistance and inductance of grid-connected line |
R, | —— | Resistance and q-axis transient reactance of SG |
T1 | —— | Time constant of hydraulic motor |
TCH | —— | Time constant of steam chest |
—— | d-axis transient time constant of SG | |
Udc | —— | Voltage of DC capacitance |
Udcref | —— | Voltage reference value of DC capacitance |
u2, i2 | —— | Voltage and current of AC grid |
ug | —— | Voltage of line capacitance |
us, is | —— | Stator voltage and current of wind turbine (WT) |
ut, ig | —— | Output voltage and current of GSC |
ur | —— | Voltage at point of common coupling (PCC) |
uo, io | —— | Output voltage and current of SG |
Xd, | —— | d-axis reactance and d-axis transient reactance of SG |
B. | —— | Subscripts |
d, q | —— | d-axis and q-axis components of rotating reference frame signal |
d2, q2 | —— | d2-axis and q2-axis components of rotating reference frame signal |
ref, 0 | —— | Reference and steady-state values of variable |
x, y | —— | x-axis and y-axis components of rotating reference frame signal |
Appendix
G1 in (2) is given as:
(A1) |
G2 in (6) is given as:
(A2) |
and in (7) and (8) are given as:
(A3) |
(A4) |
Tug and Tig in (9) and (10) are given as:
(A5) |
(A6) |
in (17) is given as:
(A7) |
in (18) is given as:
(A8) |
G12 and G13 in (21) and (22) are given as:
(A9) |
(A10) |
and in (23) are given as:
(A11) |
in (26) is given as:
(A12) |
and in (29) are given as:
(A13) |
where ; and .
and in (30) are given as:
(A14) |
(A15) |
in (31) is given as:
(A16) |
in (32) is given as:
(A17) |
Module | Parameter | Value |
---|---|---|
PMSG | Rated power Pn (MW) | 275 |
DC capacitance Cdc (mF) | 2 | |
Filter inductance Lg (H) | 0.003 | |
Filter resistance Rg (Ω) | 0.03 | |
Line resistance R1 (Ω) | 0.02 | |
Line inductance L1(H) | 0.002 | |
Line capacitance C1 (μF) | 5 | |
GSC | Outer loop proportional coefficient Kpdc | 18 |
Outer loop integral coefficient Kidc | 133 | |
Inner loop proportional coefficient Kp1 | 45 | |
Inner loop integral coefficient Ki1 | 2 | |
PLL | Proportional coefficient kpPLL | 10 |
Integral coefficient kiPLL | 30 | |
SG | Resistance R (p.u.) | 0.1 |
d-axis reactance Xd (p.u.) | 1.59 | |
q-axis transient reactance (p.u.) | 0.46 | |
d-axis transient reactance (p.u.) | 0.25 | |
Line resistance Ro (Ω) | 0.03 | |
Line inductance Lo (H) | 0.001 | |
d-axis transient time constant (s) | 0.68 | |
Inertia M | 1.759 | |
Turbine | Time constant of steam volume TCH | 0.5 |
Time constant of reheater TRH | 8 | |
Time constant of cross-pipe TCO | 1 | |
Power proportional coefficients of high-pressure cylinder FHP | 0.3 | |
Power proportional coefficients of middle pressure cylinder FIP | 0.3 | |
Power proportional coefficients of low-pressure cylinder FLP | 0.4 | |
Governor | Time constant of hydraulic motor T1 | 0.5 |
Amplification factor Kp | 1 | |
Reciprocal of unequal rate Kδ | 1 | |
Exciter | Excitation regulation gain KA | 1 |
Excitation regulation time constant TA | 0.2 | |
AC grid | Equivalent resistance R2 (Ω) | 0.01 |
Equivalent inductance L2 (H) | 0.1 |
REFERENCES
M. Dicorato, G. Forte, M. Trovato et al., “Transmission system and offshore wind farms: challenges and chances,” in Proceedings of 2018 5th International Symposium on Environment-friendly Energies and Applications, Rome, Italy, Sept. 2018, pp. 1-6. [Baidu Scholar]
J. Yan, H. Lin, Y. Feng et al., “Improved sliding mode model reference adaptive system speed observer for fuzzy control of direct-drive permanent magnet synchronous generator wind power generation system,” IET Renewable Power Generation, vol. 7, no. 1, pp. 28-35, Feb. 2013. [Baidu Scholar]
R. Li, S. Zhao, B. Gao et al., “Sub-synchronous torsional interaction of steam turbine under wind power oscillation in wind-thermal bundled transmission systems,” International Journal of Electrical Power & Energy Systems, vol. 108, pp. 445-455, Jun. 2019. [Baidu Scholar]
Q. Geng, H. Sun, X. Zhou et al., “A storage-based fixed-time frequency synchronization method for improving transient stability and resilience of smart grid,” IEEE Transactions on Smart Grid, vol. 14, no. 6, pp. 4799-4815, Nov. 2023. [Baidu Scholar]
Q. Geng, H. Sun, and X. Zhou, “Distributed fixed-time transient stability control scheme for power systems with heterogeneous dynamics,” IEEE Transactions on Power Systems, vol. 39, no. 1, pp. 1693-1710, Jan. 2024. [Baidu Scholar]
Q. Geng, H. Sun, X. Zhang et al., “Mitigation of oscillations in three phase LCL-filtered grid converters based on proportional resonance and improved model predictive control,” IEEE Transactions on Industry Applications, vol. 59, no. 2, pp. 2590-2602, Mar.-Apr. 2023. [Baidu Scholar]
K. Sun, W. Yao, J. Fang et al., “Impedance modeling and stability analysis of grid-connected DFIG-based wind farm with a VSC-HVDC,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 8, no. 2, pp. 1375-1390, Jun. 2020. [Baidu Scholar]
B. Shao, S. Zhao, B. Gao et al., “Adequacy of the single-generator equivalent model for stability analysis in wind farms with VSC-HVDC systems,” IEEE Transactions on Energy Conversion, vol. 36, no. 2, pp. 907-918, Jun. 2021. [Baidu Scholar]
W. Du, Q. Fu, and H. Wang, “Subsynchronous oscillations caused by open-loop modal coupling between VSC-Based HVDC line and power system,” IEEE Transactions on Power Systems, vol. 33, no. 4, pp. 3664-3677, Jul. 2018. [Baidu Scholar]
M. Liserre, R. Teodorescu, and F. Blaabjerg, “Stability of photovoltaic and wind turbine grid-connected inverters for a large set of grid impedance values,” IEEE Transactions on Power Electronics, vol. 21, no. 1, pp. 263-272, Jan. 2006. [Baidu Scholar]
E. Hagstrom, I. Norheim, and K. Uhlen, “Large-scale wind power integration in Norway and impact on damping in the Nordic grid,” Wind Energy, vol. 8, no. 3, pp. 375-384, Jul.-Sept. 2005. [Baidu Scholar]
T. Knüppel, J. N. Nielsen, K. H. Jensen et al., “Small-signal stability of wind power system with full-load converter interfaced wind turbine,” IET Renewable Power Generation, vol. 6, no. 2, pp.79-91, Mar. 2012. [Baidu Scholar]
K. M. Alawasa, A. R. I. Mohamed, and W. Xu, “Modeling, analysis, and suppression of the impact of full-scale wind-power converters on subsynchronous damping,” IEEE Systems Journal, vol. 7, no. 4, pp. 700-712, Dec. 2013. [Baidu Scholar]
J. Quintero, V. Vittal, G. T. Heydt et al., “The impact of increased penetration of converter control-based generators on power system modes of oscillation,” IEEE Transactions on Power Systems, vol. 29, no. 5, pp. 2248-2256, Sept. 2014. [Baidu Scholar]
W. Du, X. Chen, and H. Wang, “Power system electromechanical oscillation modes as affected by dynamic interactions from grid-connected PMSGs for wind power generation,” IEEE Transactions on Sustainable Energy, vol. 8, no. 3, pp. 1301-1312, Jul. 2017. [Baidu Scholar]
Y. Huang, X. Yuan, J. Hu et al., “DC-bus voltage control stability affected by AC-bus voltage control in VSCs connected to weak AC grids,” IEEE Journal of Emerging & Selected Topics in Power Electronics, vol. 4, no. 2, pp. 445-458, Jun. 2016. [Baidu Scholar]
W. Du, X. Chen, and H. Wang, “PLL-induced modal resonance of grid-connected PMSGs with the power system electromechanical oscillation modes,” IEEE Transactions on Sustainable Energy, vol. 8, no. 4, pp. 1581-1591, Oct. 2017. [Baidu Scholar]
H. Yuan, X. Yuan, and J. Hu, “Modeling of grid-connected VSCs for power system small-signal stability analysis in DC-link voltage control timescale,” IEEE Transactions on Power Systems, vol. 32, no. 5, pp. 3981-3991, Sept. 2017. [Baidu Scholar]
Y. Huang, X. Zhai, J. Hu et al., “Modeling and stability analysis of VSC internal voltage in DC-link voltage control timescale,” IEEE Journal of Emerging & Selected Topics in Power Electronics, vol. 6, no. 1, pp. 16-28, Mar. 2018. [Baidu Scholar]
L. Zheng and S. Ma, “DC-bus voltage damping characteristic analysis and optimization of grid-connected PMSG,” Electric Power Systems Research, vol. 216, pp. 108980-108989, Mar. 2023. [Baidu Scholar]
D. Lu, X. Wang, and F. Blaabjerg, “Impedance-based analysis of DC link voltage dynamics in voltage-source converters,” IEEE Transactions on Power Electronics, vol. 34, no. 4, pp. 3973-3985, Apr. 2019. [Baidu Scholar]
D. Wang, L. Liang, L. Shi et al., “Analysis of modal resonance between PLL and DC-link voltage control in weak-grid tied VSCs,” IEEE Transactions on Power Systems, vol. 34, no. 2, pp. 1127-1138, Mar. 2019. [Baidu Scholar]
G. O. Kalcon, G. P. Adam, O. Anaya-Lara et al., “Small signal stability analysis of multi-terminal VSC-based DC transmission systems,” IEEE Transactions on Power Systems, vol. 27, no. 4, pp.1818-1830, Nov. 2012. [Baidu Scholar]
J. Hu, Y. Huang, D. Wang et al., “Modeling of grid connected DFIG- based wind turbines for DC-link voltage stability analysis,” IEEE Transactions on Sustainable Energy, vol. 6, no. 4, pp. 1325-1336, Oct. 2015. [Baidu Scholar]
Y. Huang, X. Yuan, J. Hu et al., “Modeling of VSC connected to weak grid for stability analysis of DC-link voltage control,” IEEE Journal of Emerging & Selected Topics in Power Electronics, vol. 3, no. 3, pp. 1193-1204, Dec. 2015. [Baidu Scholar]
B. Gao, Y. Wang, S. Zeng et al., “Analysis of sub-synchronous component path and damping characteristics of D-PMSG-based wind farm incorporated into weak AC grid,” Proceedings of the CSEE, vol. 42, no. 14, pp. 5089-5103, Jul. 2022. [Baidu Scholar]
L. Liu, Y. Wang, Y. Liu et al., “Analysis of sub-synchronous interaction mechanism between D-PMSG based wind farm and LCC-HVDC,” in Proceedings of 2021 IEEE Sustainable Power and Energy Conference, Nanjing, China, Dec. 2021, pp. 203-210. [Baidu Scholar]
B. Gao, P. Deng, Y. Wang et al., “Evaluation of damping of subsynchronous interaction between direct-drive wind farm and LCC-HVDC based on the damping path analysis,” International Journal of Electrical Power &Energy Systems, vol. 144, pp. 108532-108542, Jan. 2023. [Baidu Scholar]
B. Gao, Y. Liu, R. Song et al., “Study on subsynchronous oscillation characteristics of DFIG-based wind farm integrated with LCC-HVDC system,” Proceedings of the CSEE, vol. 40, no. 11, pp. 3477-3489, Jun. 2020. [Baidu Scholar]
B. Gao, Y. Liu, B. Shao et al., “A path analysis method to study the subsynchronous oscillation mechanism in direct-drive wind farm with VSC-HVDC system,” International Journal of Electrical Power & Energy Systems, vol. 142, pp. 108328-108341, May 2022. [Baidu Scholar]
H. Weng, Y. Xu, and Z. Wang, “The impact of steam-turbine governor system on the low frequency oscillation of power grids,” Southern Power System Technology, vol. 8, no. 3, pp. 83-86, Jun. 2014. [Baidu Scholar]
Y. Xu, M. Zhang, L. Fan et al., “Small-signal stability analysis of type-4 wind in series-compensated networks,” IEEE Transactions on Energy Conversation, vol. 35, no. 1, pp. 529-538, Mar. 2018. [Baidu Scholar]
S. Zhao, N. Wang, R. Li et al., “Sub-synchronous control interaction between direct-drive PMSG-based wind farms and compensated grids,” International Journal of Electrical Power & Energy Systems, vol. 109, pp. 609-617, Jul. 2019. [Baidu Scholar]