Journal of Modern Power Systems and Clean Energy

ISSN 2196-5625 CN 32-1884/TK

网刊加载中。。。

使用Chrome浏览器效果最佳,继续浏览,你可能不会看到最佳的展示效果,

确定继续浏览么?

复制成功,请在其他浏览器进行阅读

Damping Characteristic Analysis of Wind-thermal-bundled Systems  PDF

  • Shiying Ma (Member, IEEE)
  • Liwen Zheng
Power System Department, China Electric Power Research Institute, Beijing 100192, China

Updated:2024-09-24

DOI:10.35833/MPCE.2023.000639

  • Full Text
  • Figs & Tabs
  • References
  • Authors
  • About
CITE
OUTLINE

Abstract

Wind-thermal-bundled system has emerged as the predominant type of power system, incorporating a significant proportion of renewable energy. The dynamic interaction mechanism of the system is complex, and the issue of oscillation stability is significant. In this paper, the damping characteristics of the direct current (DC) capacitance oscillation mode are analyzed using the path analysis method (PAM). This method combines the transfer-function block diagram with the damping torque analysis (DTA). Firstly, the linear models of the permanent magnet synchronous generator (PMSG), the synchronous generator (SG), and the alternating current (AC) grid are established based on the transfer functions. The closed-loop transfer-function block diagram of the wind-thermal-bundled systems is derived. Secondly, the block diagram reveals the damping path and the dynamic interaction mechanism of the system. According to the superposition principle, the transfer-function block diagram is reconstructed to achieve the damping separation. The damping coefficient of the DTA is used to quantify the effect of the interaction between the subsystems on the damping characteristics of the oscillation mode. Then, the eigenvalue analysis is used to analyze the system stability. Finally, the damping characteristic analysis is validated by time-domain simulations.

I. INTRODUCTION

IN China, wind farms are mainly concentrated in the western, northern, and eastern coastal areas. The wind power and thermal power are transmitted to central load centers through high-capacity, long-distance transmission systems [

1]. In addition, the permanent magnet synchronous generator (PMSG) has gradually become the dominant model for wind farms due to its high efficiency and low failure rate [2]. Thus, the wind-thermal-bundled system is gradually emerging as one of the primary methods for wind energy supply, offering the advantages of low cost and high efficiency [3]. However, the grid-connected PMSG system consists of multiple power electronic devices and controllers, which can lead to oscillation problems [4]-[6]. It is of great scientific and engineering importance to investigate the damping characteristics of wind-thermal-bundled systems.

Currently, several methods are available to study system oscillations, including the eigenvalue method, impedance model analysis (IMA) method, open-loop mode resonance method, damping torque analysis (DTA) method, and time-domain simulation method [

7]-[9].

1) The eigenvalue method based on the small-signal model is used to analyze the variables and subsystems related to the oscillation modes. Using the eigenvalue method, it has been found that PMSGs connected to the power system could reduce the system stability under small disturbances [

10]. In [11], based on the participation factor (PF), it is found that PMSG does not contribute to the low-frequency oscillation (LFO) of the system, which contradicts the conclusion of [10].

2) The IMA method is a frequency domain method that explains the interaction mechanism between subsystems based on their external impedance characteristics. The effect of the PMSGs on the sub-synchronous torsional interactions (SSTI) of thermal power units is investigated by IMA, taking into account the field winding and damper winding of synchronous machines. It is shown that PMSGs can lead to insufficient damping of SSTI [

12].

3) The open-loop-mode resonance analysis method has investigated the mechanism of strong interaction by studying the open-loop-mode coupling. It is found that the simultaneous involvement of the PMSG and synchronous generator (SG) in oscillation modes is due to the proximity of the converter oscillation mode (COM) and the electromechanical oscillation mode (EOM) [

13]. In [14], [15], modal resonance occurs when the open-loop mode of the phase-locked loop (PLL) and the open-loop mode of the power system approach on the complex plane, which degrades the damping of the oscillation modes.

4) In the DTA method, the studied system is equated to be second-order due to the similarity between the system and the rotor motion equation of the SG. The damping torque coefficient is used to study the vibration characteristics of the system. In [

16], based on the rotor motion equation, the voltage source converter (VSC) model is presented to describe its internal voltage dynamics in the time scale of the direct current (DC)-link voltage control.

However, the eigenvalue analysis and open-loop mode resonance analysis methods suffer from the “dimensional disaster” problem and are unable to analyze the transmission path of frequency disturbances. IMA can explain the vibration mechanism at the physical level and can be used to model the “black (gray) box” system. However, it is difficult to uncover the dynamic interactions within the system from the external impedance characteristics of the device alone. The DTA method can only study the damping characteristics of the system itself and cannot separate the dynamics of the interactions between the various links in the system. The differential algebraic equation (DAE) is used to describe the system dynamics in time-domain simulation methods, but it cannot reveal the oscillation coupling mechanism. Time-domain simulation method can be used to verify the validity of the theoretical analysis. Given the limitations of the above methods, it is crucial to explore the dynamic interaction mechanism from a new perspective.

The DTA [

17]-[19], IMA [20], and open-loop-mode resonance [21], [22] methods have been used for the analysis of the DC capacitance-dominated oscillation modes in power systems. In [17]-[19], the dynamic DC capacitance is expressed as a second-order differential equation, and the DTA method is used to analyze the stability of the DC capacitance. The definitions of equivalent inertia, synchronization power, and damping power are also discussed. It is found that the insufficient positive synchronization and damping power can lead to the instability. In [23]-[25], small-signal models of the PMSG and the doubly-fed induction generator (DFIG) are established to study the stability of the DC-link voltage. However, the dynamic interaction mechanism between the subsystems has not been revealed, and the effect of various interactions on the damping of oscillation modes cannot be quantified. To address this issue, the stability of the DC capacitance oscillation mode and the PLL oscillation mode have been investigated using the transfer-function block diagram and the damping separation method [26]-[30]. It has been found that the DC capacitance-dominated sub-synchronous oscillation (SSO) is more prone to instability when the PMSG is connected to a weak alternating current (AC) grid or a line-commutated converter-based high-voltage direct current (LCC-HVDC) system [26]-[28]. However, the external AC grid is equivalent to a voltage source, and the dynamics of the SG are not involved [26]-[30]. It is essential to develop the SG model to analyze the damping characteristics of wind-thermal-bundled systems.

In this paper, the path analysis method (PAM) is used to analyze the stability of the DC capacitance oscillation mode by combining the transfer-function block diagram and DTA. Compared with other methods, PAM can elucidate the path of disturbance transmission and the coupling relationships between the subsystems. The effect of the interaction between the subsystems on the damping of the oscillation modes is quantified by the damping reconstruction. The contributions of this paper include the following aspects.

1) The linear models (LMs) of the PMSG, SG, and AC grid are established using the transfer function equations, and the closed-loop transfer-function block diagram of the wind-thermal-bundled system is derived.

2) The closed-loop transfer-function block diagram shows the damping path and the dynamic interaction process of the subsystem. The block diagram is reconstructed to achieve damping separation based on the superposition principle. The DTA method is used to quantify the effect of dynamic interaction between subsystems on the DC capacitance oscillation mode.

3) The effect of system parameters on the damping of the DC capacitance oscillation mode is analyzed using the damping separation method and the eigenvalue method, and verified by time-domain simulation.

The remainder of this paper is organized as follows. In Section II, the LM for the wind-thermal-bundled system is established, and the transfer-function block diagram is obtained. Sections III and IV conduct damping characteristic analyses based on PAM and eigenvalue analysis method, respectively. Section III shows the coupling relationships between the subsystems based on the block diagram, which is constructed to achieve damping separation. In Section IV, the state-space model of the wind-thermal-bundled system is established, and the oscillation mode of the system is analyzed with varying parameters. In Section V, the effect of the system parameters on the damping of the DC capacitance oscillation mode is confirmed by simulation results. Conclusions are given in Section VI.

II. LM for WIND-THERMAL-BUNDLED SYSTEM

In this section, the transfer function equations are used to establish the LMs of the PMSG, SG, and AC grid. Then, the transfer-function block diagram of the wind-thermal-bundled system is derived, and its validity is verified by the step response characteristics of the electromagnetic transient model (ETM). The diagram of the wind-thermal-bundled system is shown in Fig. 1.

Fig. 1  Diagram of wind-thermal-bundled system.

In the following, the voltage ur is used as an example, and ur=urx;ury, urdq=urd;urq, urd2q2=urd2;urq2.

A. LM of PMSG

The PMSG subsystem consists of the DC capacitance, the GSC, the PLL, the filter inductance, and the grid-connected transmission lines. The control diagram of the GSC is shown in Fig. 2.

Fig. 2  Control diagram of GSC.

In Fig. 2, PIdcs and PIccs are the DC voltage outer loop control and the current inner loop control, respectively.

The dynamics of the constant DC voltage outer loop control for the GSC are given as:

Δigdref=PIdcsΔUdcΔigqref=0 (1)

where PIdcs=Kpdc+Kidc/s.

The bandwidth of the DC voltage outer loop is designed to be one-tenth of the bandwidth of the current inner loop. Therefore, the grid-side current can follow its reference value based on the current inner loop. It can be expressed as Δigd=Δigdref and Δigq=Δigqref. As the power factor of the GSC is 1, Δigqref is set to be 0. Then, both Δigq and igq are equal to 0. So, the output active power of the GSC is:

ΔPe=1.5utd0Δigd+igd0Δutd=G1ΔigdΔutd (2)

where G1 is the transfer function matrix from Δigd and Δutd to ΔPe. The expression for G1 is given in (A1) in Appendix A.

The dynamic equation for the DC capacitance is:

ΔUdc=GdcsΔPin-ΔPeGdcs=1sCdcUdc0 (3)

The dynamic equation for the PLL is:

ΔθPLL=kiPLL+skpPLLs2Δugq=HPLLsΔugq (4)

The filter line dynamics are:

ΔutdΔutq=ΔugdΔugq+Rg+sLg-ωgLgωgLgRg+sLgΔigdΔigq (5)

In (5), Δutd can be written as:

Δutd=G2sΔigdΔugd (6)

where G2s is the transfer function matrix from Δigd and Δugd to Δutd. The expression for G2s is given in (A2) in Appendix A.

The dynamic equations for the capacitance and impedance of the lines connected with the network are given as:

ΔugxΔugy=G3sΔigxΔigy+G4sΔi1xΔi1y (7)
Δi1xΔi1y=G5sΔugxΔugy+G6sΔurxΔury (8)

where G3s and G4s are the transfer function matrices from Δig and Δi1 to Δug, respectively; G5s and G6s are the transfer function matrices from Δug and Δur to Δi1, respectively; and the expressions for G3s-G6s are given in (A3) and (A4) in Appendix A.

For ug and ig, the transformation equations between the x-y frame and the d-q frame are:

ΔugdΔugq=TugΔugxΔugyΔθPLL (9)
ΔigxΔigy=TigΔigdΔigqΔθPLL (10)

where Tug is the transfer function matrix from Δug and ΔθPLL to Δugdq; and Tig is the transfer function matrix from Δigdq and ΔθPLL to Δig. The detailed expressions of Tug and Tig are given in (A5) and (A6) in Appendix A.

Combining (7), (8), and (10) yields Δi1:

Δi1xΔi1y=G7sΔigdΔθPLLΔurxΔury (11)

where G7s is the transfer function matrix from Δigd, ΔθPLL, Δur to Δi1. As G7s is complicated, it will not be listed in this paper.

Combining (7), (9), and (10), we can obtain Δugdq as:

ΔugdΔugq=G8sΔigdΔθPLLΔi1xΔi1y (12)

where G8s is the transfer function matrix from Δigd, ΔθPLL, Δi1 to Δugdq.

Based on (1)-(4), (6), (11), and (12), the LM of the PMSG is shown in Fig. 3. The input variables are Δurx, Δury, and ΔPin, while the output variables are Δilx and Δily.

Fig. 3  LM of PMSG.

B. LM of SG

The voltage equation for SG is given as:

Δuod2=-RΔiod2-Xq'Δioq2Δuoq2=ΔEq'-RΔioq2+Xd'Δiod2 (13)

The third-order dynamic model of SG is given as:

sΔδ=ω0ΔωMsΔω=ΔPm-ΔPt-DΔωTd0'sΔEq'=ΔEfd-ΔEq'+Xd-Xd'Δiod2 (14)

Considering the governor and turbine of SG, the relationship between the Δω and ΔPm is:

ΔPm=-FHPKpKδ1+T1s1+TCHsΔω=-Gω-PmsΔω (15)

In the d2-q2 frame, the dynamic equation of the SG grid-connected transmission line is:

Δuod2Δuoq2=Δurd2Δurq2+Ro+sLo-ωgLoωgLoRo+sLoΔiod2Δioq2 (16)

Combining (13) and (16), we can obtain:

Δiod2Δioq2=-R-Ro-sLo-Xq'+ωgLoXd'-ωgLo-R-Ro-sLo-1Δurd2Δurq2-ΔEq' (17)

Substituting (13) and (17) into the third formula of (14), we can obtain:

ΔEq'=G9sΔurd2Δurq2 (18)

where G9s is the transfer function matrix from Δurd2q2 to ΔEq', and the detailed expression of G9s is given in (A7) in Appendix A.

By substituting (18) into (16), Δiod2q2 can be written as:

Δiod2Δioq2=G10sΔurd2Δurq2 (19)

where G10s is the transfer function from Δurd2q2 to Δiod2q2, and the detailed expression of G10s is given in (A8) in Appendix A.

The active power of SG is:

ΔPt=uod20Δiod2+iod20Δuod2+uoq20Δioq2+ioq20Δuoq2 (20)

By substituting (16) and (19) into (20), ΔPt is obtained as:

ΔPt=G11sΔurd2Δurq2 (21)

where G11s is the transfer function matrix from Δurd2q2 to ΔPt.

For Δur and Δio, the conversion relation between the d2-q2 frame and the x-y frame is given as:

Δurd2Δurq2=G12ΔurxΔuryΔδ (22)
ΔioxΔioy=G13Δiod2Δioq2Δδ (23)

where G12 is the transfer function matrices from Δur and Δδ to Δurd2q2; and G13 is the transfer function matrices from Δiod2q2 and Δδ to Δio. The detailed expressions of G12 and G13 are given in (A9) and (A10) in Appendix A, respectively.

Based on (14), (19), (21)-(23), the LM of SG is shown in Fig. 4. The input variables are Δurx and Δury, while the output variables are Δiox and Δioy.

Fig. 4  LM of SG.

C. LM of AC Grid

The dynamics of the AC grid are given as:

Δi2xΔi2y=G14sΔurxΔury+G15sΔu2xΔu2y (24)

where G14s and G15s are the transfer function matrices from Δur and Δu2 to Δi2, respectively. The expressions of G14s and G15s are given in (A11) in Appendix A.

Omitting the change of Δu2, (24) can be rewritten as:

Δi2xΔi2y=G14sΔurxΔury (25)

According to Fig. 1, (26) is obtained as:

Δi2xΔi2y=Δi1xΔi1y+ΔioxΔioy (26)

The combination of (25) and (26) gives:

ΔurxΔury=G16sΔi1xΔi1y+ΔioxΔioy (27)

where G16s is the transfer function matrix from Δi1 and Δio to Δur. The detailed expression of G16s is given in (A12) in Appendix A.

Based on (27), the aggregated LM of the AC grid is shown in Fig. 5. The input variables are Δio and Δi1, while the output variables are Δur.

Fig. 5  Aggregated LM of AC grid.

D. Closed-loop Transfer Function Model

By combining (2), (3), (5), (11), and (12) to eliminate the intermediate variables Δi1, ΔθPLL, Δig, and Δut, the output power of the PMSG is calculated as:

ΔPe=Gp1sΔUdc+Gp2sΔurxΔury (28)

where Gp1s is the transfer function from ΔUdc to ΔPe; and Gp2s is the transfer function matrix from Δur to ΔPe.

By combining (1), (4), (11), and (12) to eliminate the intermediate variables ΔθPLL and Δig, Δi1 can be rewritten as:

Δi1xΔi1y=Gi1sΔUdc+Gi2sΔurxΔury (29)

where Gi1s and Gi2s are the transfer function matrices from ΔUdc and Δur to Δi1, respectively.

Based on (3), (28), and (29), the aggregated LM of the PMSG is shown in Fig. 6. The input variables are Δur and ΔPin, while the output variables are Δi1.

Fig. 6  Aggregated LM of PMSG.

By substituting (22) into (21), the active power of SG is obtained as:

ΔPt=Gp3sΔδ+Gp4sΔurxΔury (30)

where Gp3s is the transfer function from Δδ to ΔPt; and Gp4s is the transfer function matrix from Δur to ΔPt. The detailed expressions of Gp3s and Gp4s are given in (A13) in Appendix A.

Combining (19), (22), and (23), we can obtain:

ΔioxΔioy=Gi3sΔδ+Gi4sΔurxΔury (31)

where Gi3s and Gi4s are the transfer function matrices from Δδ and Δur to Δio, respectively. The expressions of Gi3s and Gi4s are given in (A14) and (A15) in Appendix A, respectively.

Substituting (15) into (14), we obtain the transfer function from ΔPt to Δδ:

GP-δs=1Ms2+Ds+sGω-Pms (32)

Based on (14) and (30)-(32), the aggregated LM of SG is shown in Fig. 7. The input variables are Δur, while the output variables are Δio.

Fig. 7  Aggregated LM of SG.

According to (3), (14), and (27)-(32), the transfer-function block diagram of the wind-thermal-bundled system is shown in Fig. 8.

Fig. 8  Transfer-function block diagram of wind-thermal-bundled system.

From the above derivation, it is clear that the transfer-function block diagram of the system before and after the polymerization corresponds to each other, and the dynamic interaction analysis can be performed based on the transfer-function block diagram.

E. Validation of LM

Before analyzing the dynamic interaction mechanism, the accuracy of the LM in MATLAB should be validated using the ETM in DIgSILENT/PowerFactory. The reference DC voltage Udcref has a step change from 1.1 p.u. to 1.05 p.u. at t=1 s, and the response curves of the system under LM and ETM are shown in Fig. 9. In Fig. 9, it is shown that the LM response is consistent with the ETM response, which verifies the correctness of the LM.

Fig. 9  Response curves following a change of Udcref from 1.1 p.u. to 1.05 p.u.. (a) Pt of SG. (b) Io of SG. (c) Pe of GSC. (d) Udc of PMSG.

III. DAMPING CHARACTERISTIC ANALYSIS BASED ON PAM

In this section, the analysis of the damping path is presented based on the transfer-function block diagram. The block diagram is reconstructed to isolate the interaction damping. The factors influencing the damping characteristics are studied based on the damping reconstruction.

A. Damping Path Analysis

The block diagram of the damping path analysis, as shown in Fig. 10, clearly illustrates the relationship between each state variable and the corresponding link. This is beneficial for separating the disturbance transfer paths within the system. In the transfer function block diagram, the closed loop passing through the transfer function Gdcs is defined as the SSO damping path. In Fig. 10, there are two damping paths which are represented by red and purple solid ovals, respectively, and the arrows indicate the direction of the disturbance transfer.

Fig. 10  Block diagram of damping path analysis.

Damping path 1 can be described as the path through which the disturbance is transmitted from ΔUdc to ΔPe, assuming that ΔPin remains constant.

Damping path 1 consists of the transfer functions Gdcs and Gp1s. This indicates that path 1 is related to the DC capacitance of the PMSG and the outer loop control of the GSC. Damping path 1 is referred to as the internal oscillation transfer path of the PMSG.

Damping path 2 can be described as follows. When ΔPe changes, the disturbance is transmitted from ΔUdc to Δil, then from Δil to Δur, and finally from Δur to ΔPe. Damping path 2 passes through three subsystems: PMSG, SG, and AC grid, and includes two closed-loop paths denoted as a and b, which are indicated by oval dashed lines. The closed-loop path a passes through Δil and Δur, and consists of the transfer function matrices Gi2s and G16s, which represent the interaction between the PMSG and the AC grid. The closed loop path b passes through Δio and Δur and consists of the transfer function matrices Gi4s and G16s, reflecting the interaction between the AC system and the SG. The closed loops a and b interact at the PCC voltage Δur to form a closed crossed loop. When the voltage Δur is disturbed, the currents Δil and Δio change due to the existence of closed loops a and b, which in turn affect the dynamics of Δur. Thus, damping path 2 is referred to as the oscillation coupling path among the PMSG, SG, and AC grid.

Furthermore, the interaction processes can be divided into two groups: the controller interaction in the PMSG, and the interaction among the PMSG, SG, and AC grid. The controller interaction in the PMSG can be understood as the dynamic process of controller interaction in the PMSG system, which is caused by disturbances through a closed loop (damping path 1). The interaction between the PMSG, the SG, and the AC grid can be understood as the dynamic interplay between the subsystems triggered by voltage and current disturbances at the PCC driven by the closed loop (damping path 2).

B. Damping Separation Method

According to the superposition principle of linear systems, the transfer function block diagram is reconstructed, and the damping provided by the dynamic interaction is quantified. The damping separation procedure is as follows.

Step 1:   based on (14) and (30), we can obtain (33) and Fig. 11(a).

Fig. 11  Damping reconstruction process. (a) Step 1. (b) Step 2. (c) Step 3. (d) Step 4.

Δδ=GmsΔurxΔury (33)

where Gms is the transfer function matrix from Δur to Δδ. The expression of Gms is given in (A16) in Appendix A.

Step 2:   combining (28) and (21), we obtain (34) and Fig. 11(b).

ΔioxΔioy=GnsΔurxΔury (34)

where Gns is the transfer function matrix from Δur to Δio. The expression of Gns is given in (A17) in Appendix A.

Step 3:   combining (27), (29), and (34), we obtain (35) and Fig. 11(c).

ΔurxΔury=GosΔUdc (35)

where Gos is the transfer function matrix from ΔUdc to Δur.

The open-loop transfer function matrix Gos represents the interaction between the PMSG and the SG and the interaction between the PMSG and the AC system. If Δio=0, i.e., the SG is not connected to the system and the interaction between the PMSG and the SG is not considered, the block diagram is simplified. The corresponding open loop transfer function matrix Go1s is obtained by substituting (29) into (27). Go1s represents the interaction between the PMSG and the AC grid. According to the superposition principle of linear systems, Gos is subtracted from Go1s to obtain Go2s, where Go2s represents the interaction between the PMSG and the SG. The expressions for Gos, Go1s, and Go2s are given in (36), and the transfer function block diagram is shown in Fig. 11(c).

Gos=I-G16sGi2s+Gns-1G16sGi1sGo1s=I-G16sGi2s-1G16sGi1sGo2s=Gos-Go1s (36)

Step 4:   when ΔPin is selected as the input variable and ΔUdc is selected as the output variable, three transfer functions from ΔUdc to the variables ΔPe-ΔPin and ΔPe are obtained using the damping separation method, as shown in Fig. 11(d) and (37).

Gz1s=Gp1sGz21s=Gp2sGo1sGz22s=Gp2sGo2s (37)

where Gz1s is the internal damping of the PMSG; Gz21s is the damping of the DC capacitance oscillation influenced by the interaction between the PMSG and the AC grid; and Gz22s is the damping influenced by the interaction between the PMSG and the SG system.

The corresponding damping coefficient can be calculated from:

Z1=ImjωdGz1jωd/ωdZ21=ImjωdGz21jωd/ωdZ22=ImjωdGz22jωd/ωdZ2=Z21+Z22 (38)

where Z1 is the PMSG self-damping coefficient; Z21 is the PMSG-grid interaction damping coefficient; Z22 is the PMSG-SG interaction damping coefficient; and Z2 is the interaction damping coefficient. The total damping coefficient of the system is Z=Z1+Z2.

C. Analysis of Influence Factors

1) Proportional Coefficient of DC Voltage Outer Loop of GSC

To study the influence of the proportional coefficient of DC voltage outer loop of GSC control Kpdc on the damping coefficient, Fig. 12(a) shows the frequency characteristic curves of damping coefficients Z21 and Z22 at different Kpdc. Figure 12(b) shows the frequency characteristic curves of self-damping coefficient Z1, interaction damping coefficient Z2, and total damping coefficient Z at different Kpdc. The values of Kpdc are 12, 18, and 25, respectively. The arrow indicates the change direction of the frequency characteristic curves with increasing Kpdc.

Fig. 12  Damping characteristic analysis with change of Kpdc. (a) Frequency characteristic curves of Z21 and Z22. (b) Frequency characteristic curves of Z1, Z2, and Z.

As shown in Fig.12(a), as Kpdc increases, the interaction damping between the PMSG and the SG increases, and the interaction damping between the PMSG and the AC grid decreases. As shown in Fig.12(b), as Kpdc increases, the frequency characteristic curves of Z1, Z2, and Z move upward, indicating that the increase in Kpdc causes the self-damping coefficient Z1, the interaction damping coefficient Z2, and the total damping coefficient Z to increase.

2) Integral Coefficient of DC Voltage Outer Loop of GSC

To study the influence of the integral coefficient of DC voltage outer loop of GSC control Kidc on the damping coefficient, Fig. 13(a) shows the frequency characteristic curves of damping coefficients Z21 and Z22 at different Kidc. Figure 13(b) shows the frequency characteristic curves of self-damping coefficient Z1, interaction damping coefficient Z2, and total damping coefficient Z at different Kidc. The values of Kidc are 133, 233, and 333, respectively. The arrow indicates the change direction of the frequency characteristic curves as Kidc increases.

Fig. 13  Damping characteristic analysis with change of Kidc. (a) Frequency characteristic curves of Z21 and Z22. (b) Frequency characteristic curves of Z1, Z2, and Z.

As shown in Fig. 13(a), as Kidc increases, the interaction damping coefficient between the PMSG and the SG increases, and the interaction damping coefficient between the PMSG and the AC grid decreases. As shown in Fig. 13(b), as Kidc increases, the frequency characteristic curve of Z1 moves upward, indicating that the positive damping effect provided by the PMSG increases. The frequency characteristic curve of Z2 moves downward, indicating that the interaction damping decreases. The total damping coefficient Z decreases and the system stability is weakened.

3) Grid Strength

To study the influence of short-circuit ratio (SCR) on the damping coefficient, Fig. 14(a) shows the frequency characteristic curves of damping coefficients Z21 and Z22 under different SCRs. Figure 14(b) shows the frequency characteristic curves of self-damping coefficient Z1, interaction damping coefficient Z2, and total damping coefficient Z under different SCR. The values of SCR are 1, 2, and 3, respectively. The arrow indicates the change direction of the frequency characteristic curves as the SCR increases.

Fig. 14  Damping characteristic analysis with change of SCR. (a) Frequency characteristic curves of Z21 and Z22. (b) Frequency characteristic curves of Z1, Z2, and Z.

As shown in Fig. 14(a), as the SCR increases, the interaction damping between the PMSG and the SG decreases, and the interaction damping between the PMSG and the AC power grid increases. As shown in Fig. 14(b), the frequency characteristic curve of Z1 remains unchanged as the SCR increases, indicating that the positive damping effect provided by the PMSG is independent of the power system strength. The frequency characteristic curves of Z2 and Z move upward, indicating that the interaction damping and the total damping increase.

4) Time Constant of Hydraulic Motor T1

To study the influence of the time constant of the hydraulic motor T1 on the damping coefficient, Fig. 15(a) shows the frequency characteristic curves of damping coefficients Z21 and Z22 under different T1. Figure 15(b) shows the frequency characteristic curves of self-damping coefficient Z1, interaction damping coefficient Z2, and total damping coefficient Z under different T1. The values of T1 are 0.5, 2, and 5, respectively. The arrow indicates the change direction of the frequency characteristic curves as T1 increases.

Fig. 15  Damping characteristic analysis with change of T1. (a) Frequency characteristic curves of Z21 and Z22. (b) Frequency characteristic curves of Z1, Z2, and Z.

As shown in Fig. 15(a), as T1 increases, the interaction damping between the PMSG and the SG decreases, and the interaction damping between the PMSG and the AC grid remains unchanged. As shown in Fig. 15(b), the frequency characteristic curve of Z1 remains unchanged as T1 increases. The frequency characteristic curves of Z2 and Z move downward, indicating that the interaction damping and the total damping decrease.

IV. DAMPING CHARACTERISTIC ANALYSIS BASED ON EIGENVALUE ANALYSIS METHOD

A. Eigenvalue Analysis

The small-signal models for PMSG and SG have been extensively studied, e.g., [

31]-[33], and will not be discussed here. The state space model for the system is given as:

dΔXdt=AΔX+BΔu (39)

Based on (37) and the parameters in Appendix B Table BI, the primary oscillation modes of the wind-thermal-bundled system are shown in Table I.

TABLE I  OSCILLATION MODES OF WIND-THERMAL-BUNDLED SYSTEM
Oscillation modeEigenvalueOscillation frequency (Hz)Damping ratio
λ1,2 -3.35±j15.870 2.53 0.2063
λ3,4 20.77±j53.460 8.51 -0.3621
λ5,6 -10.50±j90.670 14.43 0.1150
λ7,8 -12.59±j321.130 51.11 0.0392
λ9,10 -22.53±j356.598 56.75 0.0631
λ11,12 -66.48±j1799.400 286.39 0.0369

As shown in Table I, the system has six oscillation modes: one LFO mode λ1,2, two SSO modes λ3,4, λ5,6, and three medium-high frequency oscillation modes λ7,8, λ9,10, and λ11,12. The real parts of modes λ1,2, λ5,6, λ7,8, λ9,10, and λ11,12 are negative, i.e., these modes are stable oscillation modes. The real part of the mode λ3,4 is positive, i.e., mode 5 is an unstable SSO mode.

The normalized PFs of the oscillation modes have been calculated, and it has been shown that the oscillation mode λ3,4 is associated with the DC voltage control of the GSC. The effect of the system parameters on the mode λ3,4 is studied.

B. Influence of Parameters on Oscillation Mode

1) Proportional Coefficient of DC Voltage Outer Loop of GSC

Figure 16 shows the variation of the oscillation mode λ3,4 and the damping ratio as Kpdc changes from 4 to 16. In Fig. 16, the arrows indicate the variation of λ3,4 and damping ratio as Kpdc increases.

Fig. 16  Variation of oscillation mode λ3,4 and damping ratio with different Kpdc. (a) Oscillation mode. (b) Damping ratio.

As shown in Fig. 16, the increase in Kpdc causes the oscillation mode λ3,4 to shift to the left, resulting in an increase in the damping ratio and indicating improved stability.

2) Integral Coefficient of DC Voltage Outer Loop of GSC

Figure 17 shows the variation of the oscillation mode λ3,4 and the damping ratio as Kidc changes from 40 to 120. In Fig. 17, the arrows indicate the variation of λ3,4 and damping ratio as Kidc increases.

Fig. 17  Variation of oscillation mode λ3,4 and damping ratio with different Kidc. (a) Oscillation mode. (b) Damping ratio.

Figure 17 shows that as Kidc increases, λ3,4 moves to the right and the damping ratio decreases, indicating a gradual destabilization of the system.

V. SIMULATION RESULTS

In this section, the wind-thermal-bundled system is constructed in DIgSILENT. At t=1 s, Kidc is changed from 133 to 1000 to excite SSO. Other parameters are in accordance with Appendix B Table BI. The DC capacitance voltage curves with different parameters are shown to validate the above analysis. When the system is disturbed, the DC voltage curves with different Kpdc, Kidc, SCR, and T1 are shown in Fig. 18.

Fig. 18  DC voltage response curves with different parameters. (a) Kpdc. (b) Kidc. (c) SCR. (d) T1.

In Fig. 18, it can be observed that the DC voltage fluctuation decreases as Kpdc or SCR increases. The DC voltage fluctuation increases as Kidc or T1 increases. The results of the damping characteristics analysis are validated by time-domain simulations.

VI. CONCLUSION

The damping characteristics of the wind-thermal-bundled system are analyzed using the PAM. The conclusions are given as follows.

1) The LMs for the PMSG, SG, and AC grid are established, respectively, and the LMs of the subsystems are connected to construct the transfer-function block diagram of the system.

2) The damping path analysis is presented based on the transfer-function block diagram. The interaction mechanism between the subsystems can be interpreted as a dynamic process driven by voltage disturbances and current disturbances at the PCC.

3) Based on the damping separation, the total damping of the DC capacitance-dominated oscillation mode can be divided into three parts: PMSG internal damping coefficient, PMSG-SG interaction damping coefficient, and PMSG-grid interaction damping coefficient.

4) The effect of the parameters on the damping characteristics is analyzed using the damping separation method and the eigenvalue analysis method, respectively. The analysis shows that Kpdc and SCR have a positive effect on the damping of the DC capacitance-dominated oscillation mode, while Kidc and T1 have a negative effect. The analysis results are of great importance for practical engineering.

NOMENCLATURE

Symbol —— Definition
A. —— Variables
ωg —— Grid frequency
ω0 —— Rated frequency
δ, ω —— Power angle and frequency of synchronous generator (SG)
ΔθPLL —— Phase locked loop (PLL) output angle
ΔX —— State variable matrix
Δu —— Input variable matrix
A —— Coefficient matrix
B —— Input matrix
C1 —— Line capacitance
Cdc —— Direct current (DC) capacitance between machine-side converter (MSC) and grid-side converter (GSC)
Efd —— Forced no-load electromotive force of SG
Eq' —— q-aixs transient electromotive force of SG
FHP —— Power proportional coefficient of high-pressure cylinder
HPLL(s) —— Transfer function from Δugq to Δθpll
Kδ —— Reciprocal of unequal rate
Kp —— Proportional coefficient of proportional-integral-derivative (PID) link in governor system
Kpdc, Kidc —— Proportional and integral coefficients of constant DC voltage control
kpPLL, kiPLL —— Proportional coefficient and integral coefficient of PLL
M, D —— Inertia and damping coefficients of SG
Pe —— Input power of GSC
Pin —— Output active power of MSC
Pm, Pt —— Mechanical power and electromagnetic power of SG
R1, L1, i1 —— Grid-side resistance, inductance, and current of permanent magnet synchronous generator (PMSG)
R2, L2 —— Equivalent resistance and inductance of alternating current (AC) grid
Rg, Lg —— Filter resistance and inductance of PMSG
Ro, Lo —— Resistance and inductance of grid-connected line
R, Xq' —— Resistance and q-axis transient reactance of SG
T1 —— Time constant of hydraulic motor
TCH —— Time constant of steam chest
Td0' —— d-axis transient time constant of SG
Udc —— Voltage of DC capacitance
Udcref —— Voltage reference value of DC capacitance
u2, i2 —— Voltage and current of AC grid
ug —— Voltage of line capacitance
us, is —— Stator voltage and current of wind turbine (WT)
ut, ig —— Output voltage and current of GSC
ur —— Voltage at point of common coupling (PCC)
uo, io —— Output voltage and current of SG
Xd, Xd' —— d-axis reactance and d-axis transient reactance of SG
B. —— Subscripts
d, q —— d-axis and q-axis components of rotating reference frame signal
d2, q2 —— d2-axis and q2-axis components of rotating reference frame signal
ref, 0 —— Reference and steady-state values of variable
x, y —— x-axis and y-axis components of rotating reference frame signal

Appendix

APPENDIX A

G1 in (2) is given as:

G1s=1.5utd01.5igd0 (A1)

G2 in (6) is given as:

G2s=sLg1 (A2)

G3s and G4s in (7) and (8) are given as:

G3s=-G4s=GC1sGC2s-GC2sGC1sGC1s=1C1s+ω02/sGC2s=ω0GC1ss (A3)
G5s=-G6s=GL1sGL2s-GL2sGL1sGL1s=R1+sL1L12s2+L12ω02+2sL1R1+R12GL2s=ω0L1L12s2+L12ω02+2sL1R1+R12 (A4)

Tug and Tig in (9) and (10) are given as:

Tug=cosθPLL0sinθPLL0k1-sinθPLL0cosθPLL0k2Tig=cosθPLL0-sinθPLL0k3sinθPLL0cosθPLL0k4 (A5)
k1=-ugx0sinθPLL0+ugy0cosθPLL0k2=-ugx0cosθPLL0-ugy0sinθPLL0k3=-igd0sinθPLL0-igq0cosθPLL0k4=igd0cosθPLL0-igq0sinθPLL0 (A6)

G9s in (17) is given as:

G9s=a9_1a9_2a9_1=Td0's+1+Xd-Xd'a12-1Xd-Xd'a11a9_2=Td0's+1+Xd-Xd'a12-1Xd-Xd'a12a11a12a21a22=-R-Ro-sLo-Xq'+ωgLoXd'-ωgLo-R-Ro-sLo-1 (A7)

G10s in (18) is given as:

G10s=a10_1a10_2a10_3a10_4a10_1=a11+a12a9_1a10_2=a12+a12a9_2a10_3=a21+a22a9_1a10_4=a22+a22a9_2 (A8)

G12 and G13 in (21) and (22) are given as:

G12=cosδ0sinδ0k5-sinδ0cosδ0k6G13=cosδ0-sinδ0k7sinδ0cosδ0k8 (A9)
k5=-urx0sinδ0+ury0cosδ0k6=-urx0cosδ0-ury0sinδ0k7=-iod20sinδ0-ioq20cosδ0k8=iod20cosδ0-ioq20sinδ0 (A10)

G14s and G15s in (23) are given as:

G14s=-G15s=GL5sGL6s-GL6sGL5sGL5s=R2+sL2L22s2+L22ω02+2sL2R2+R22GL6s=ω0L2L22s2+L22ω02+2sL2R2+R22 (A11)

G16s in (26) is given as:

G16s=G14-1s (A12)

Gp3s and Gp4s in (29) are given as:

Gp3s=a11_1k5+a11_2k6Gp4s=ap4_1ap4_2ap4_1=a11_1cosδ0-a11_2sinδ0ap4_2=a11_1sinδ0+a11_2cosδ0 (A13)

where a11_1=G111,1; and a11_2=G111,2.

Gi3s and Gi4s in (30) are given as:

Gi3s=ai3_1ai3_2Gi4s=ai4_1ai4_2ai4_3ai4_4 (A14)
ai3_1=-sinδ0a10_2k5+cosδ0a10_1k6+k7ai3_2=cosδ0a10_2k5+sinδ0a10_1k6+k8ai4_1=-sinδ0cosδ0a10_1+a10_2ai4_2=-sinδ02a10_2+cosδ02a10_1ai4_3=cosδ02a10_2-sinδ02a10_1ai4_4=sinδ0cosδ0a10_1+a10_2 (A15)

Gms in (31) is given as:

Gms=-1+Gp-δsGp3s-1Gp4s (A16)

Gns in (32) is given as:

Gns=Gi3sGms+Gi4s (A17)

APPENDIX B

TABLE BI  PARAMETERS OF WIND-THERMAL-BUNDLED SYSTEM
ModuleParameterValue
PMSG Rated power Pn (MW) 275
DC capacitance Cdc (mF) 2
Filter inductance Lg (H) 0.003
Filter resistance Rg (Ω) 0.03
Line resistance R1 (Ω) 0.02
Line inductance L1(H) 0.002
Line capacitance C1 (μF) 5
GSC Outer loop proportional coefficient Kpdc 18
Outer loop integral coefficient Kidc 133
Inner loop proportional coefficient Kp1 45
Inner loop integral coefficient Ki1 2
PLL Proportional coefficient kpPLL 10
Integral coefficient kiPLL 30
SG Resistance R (p.u.) 0.1
d-axis reactance Xd (p.u.) 1.59
q-axis transient reactance Xq' (p.u.) 0.46
d-axis transient reactance Xd' (p.u.) 0.25
Line resistance Ro (Ω) 0.03
Line inductance Lo (H) 0.001
d-axis transient time constant Td' (s) 0.68
Inertia M 1.759
Turbine Time constant of steam volume TCH 0.5
Time constant of reheater TRH 8
Time constant of cross-pipe TCO 1
Power proportional coefficients of high-pressure cylinder FHP 0.3
Power proportional coefficients of middle pressure cylinder FIP 0.3
Power proportional coefficients of low-pressure cylinder FLP 0.4
Governor Time constant of hydraulic motor T1 0.5
Amplification factor Kp 1
Reciprocal of unequal rate Kδ 1
Exciter Excitation regulation gain KA 1
Excitation regulation time constant TA 0.2
AC grid Equivalent resistance R2 (Ω) 0.01
Equivalent inductance L2 (H) 0.1

REFERENCES

1

M. Dicorato, G. Forte, M. Trovato et al., “Transmission system and offshore wind farms: challenges and chances,” in Proceedings of 2018 5th International Symposium on Environment-friendly Energies and Applications, Rome, Italy, Sept. 2018, pp. 1-6. [Baidu Scholar] 

2

J. Yan, H. Lin, Y. Feng et al., “Improved sliding mode model reference adaptive system speed observer for fuzzy control of direct-drive permanent magnet synchronous generator wind power generation system,” IET Renewable Power Generation, vol. 7, no. 1, pp. 28-35, Feb. 2013. [Baidu Scholar] 

3

R. Li, S. Zhao, B. Gao et al., “Sub-synchronous torsional interaction of steam turbine under wind power oscillation in wind-thermal bundled transmission systems,” International Journal of Electrical Power & Energy Systems, vol. 108, pp. 445-455, Jun. 2019. [Baidu Scholar] 

4

Q. Geng, H. Sun, X. Zhou et al., “A storage-based fixed-time frequency synchronization method for improving transient stability and resilience of smart grid,” IEEE Transactions on Smart Grid, vol. 14, no. 6, pp. 4799-4815, Nov. 2023. [Baidu Scholar] 

5

Q. Geng, H. Sun, and X. Zhou, “Distributed fixed-time transient stability control scheme for power systems with heterogeneous dynamics,” IEEE Transactions on Power Systems, vol. 39, no. 1, pp. 1693-1710, Jan. 2024. [Baidu Scholar] 

6

Q. Geng, H. Sun, X. Zhang et al., “Mitigation of oscillations in three phase LCL-filtered grid converters based on proportional resonance and improved model predictive control,” IEEE Transactions on Industry Applications, vol. 59, no. 2, pp. 2590-2602, Mar.-Apr. 2023. [Baidu Scholar] 

7

K. Sun, W. Yao, J. Fang et al., “Impedance modeling and stability analysis of grid-connected DFIG-based wind farm with a VSC-HVDC,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 8, no. 2, pp. 1375-1390, Jun. 2020. [Baidu Scholar] 

8

B. Shao, S. Zhao, B. Gao et al., “Adequacy of the single-generator equivalent model for stability analysis in wind farms with VSC-HVDC systems,” IEEE Transactions on Energy Conversion, vol. 36, no. 2, pp. 907-918, Jun. 2021. [Baidu Scholar] 

9

W. Du, Q. Fu, and H. Wang, “Subsynchronous oscillations caused by open-loop modal coupling between VSC-Based HVDC line and power system,” IEEE Transactions on Power Systems, vol. 33, no. 4, pp. 3664-3677, Jul. 2018. [Baidu Scholar] 

10

M. Liserre, R. Teodorescu, and F. Blaabjerg, “Stability of photovoltaic and wind turbine grid-connected inverters for a large set of grid impedance values,” IEEE Transactions on Power Electronics, vol. 21, no. 1, pp. 263-272, Jan. 2006. [Baidu Scholar] 

11

E. Hagstrom, I. Norheim, and K. Uhlen, “Large-scale wind power integration in Norway and impact on damping in the Nordic grid,” Wind Energy, vol. 8, no. 3, pp. 375-384, Jul.-Sept. 2005. [Baidu Scholar] 

12

T. Knüppel, J. N. Nielsen, K. H. Jensen et al., “Small-signal stability of wind power system with full-load converter interfaced wind turbine,” IET Renewable Power Generation, vol. 6, no. 2, pp.79-91, Mar. 2012. [Baidu Scholar] 

13

K. M. Alawasa, A. R. I. Mohamed, and W. Xu, “Modeling, analysis, and suppression of the impact of full-scale wind-power converters on subsynchronous damping,” IEEE Systems Journal, vol. 7, no. 4, pp. 700-712, Dec. 2013. [Baidu Scholar] 

14

J. Quintero, V. Vittal, G. T. Heydt et al., “The impact of increased penetration of converter control-based generators on power system modes of oscillation,” IEEE Transactions on Power Systems, vol. 29, no. 5, pp. 2248-2256, Sept. 2014. [Baidu Scholar] 

15

W. Du, X. Chen, and H. Wang, “Power system electromechanical oscillation modes as affected by dynamic interactions from grid-connected PMSGs for wind power generation,” IEEE Transactions on Sustainable Energy, vol. 8, no. 3, pp. 1301-1312, Jul. 2017. [Baidu Scholar] 

16

Y. Huang, X. Yuan, J. Hu et al., “DC-bus voltage control stability affected by AC-bus voltage control in VSCs connected to weak AC grids,” IEEE Journal of Emerging & Selected Topics in Power Electronics, vol. 4, no. 2, pp. 445-458, Jun. 2016. [Baidu Scholar] 

17

W. Du, X. Chen, and H. Wang, “PLL-induced modal resonance of grid-connected PMSGs with the power system electromechanical oscillation modes,” IEEE Transactions on Sustainable Energy, vol. 8, no. 4, pp. 1581-1591, Oct. 2017. [Baidu Scholar] 

18

H. Yuan, X. Yuan, and J. Hu, “Modeling of grid-connected VSCs for power system small-signal stability analysis in DC-link voltage control timescale,” IEEE Transactions on Power Systems, vol. 32, no. 5, pp. 3981-3991, Sept. 2017. [Baidu Scholar] 

19

Y. Huang, X. Zhai, J. Hu et al., “Modeling and stability analysis of VSC internal voltage in DC-link voltage control timescale,” IEEE Journal of Emerging & Selected Topics in Power Electronics, vol. 6, no. 1, pp. 16-28, Mar. 2018. [Baidu Scholar] 

20

L. Zheng and S. Ma, “DC-bus voltage damping characteristic analysis and optimization of grid-connected PMSG,” Electric Power Systems Research, vol. 216, pp. 108980-108989, Mar. 2023. [Baidu Scholar] 

21

D. Lu, X. Wang, and F. Blaabjerg, “Impedance-based analysis of DC link voltage dynamics in voltage-source converters,” IEEE Transactions on Power Electronics, vol. 34, no. 4, pp. 3973-3985, Apr. 2019. [Baidu Scholar] 

22

D. Wang, L. Liang, L. Shi et al., “Analysis of modal resonance between PLL and DC-link voltage control in weak-grid tied VSCs,” IEEE Transactions on Power Systems, vol. 34, no. 2, pp. 1127-1138, Mar. 2019. [Baidu Scholar] 

23

G. O. Kalcon, G. P. Adam, O. Anaya-Lara et al., “Small signal stability analysis of multi-terminal VSC-based DC transmission systems,” IEEE Transactions on Power Systems, vol. 27, no. 4, pp.1818-1830, Nov. 2012. [Baidu Scholar] 

24

J. Hu, Y. Huang, D. Wang et al., “Modeling of grid connected DFIG- based wind turbines for DC-link voltage stability analysis,” IEEE Transactions on Sustainable Energy, vol. 6, no. 4, pp. 1325-1336, Oct. 2015. [Baidu Scholar] 

25

Y. Huang, X. Yuan, J. Hu et al., “Modeling of VSC connected to weak grid for stability analysis of DC-link voltage control,” IEEE Journal of Emerging & Selected Topics in Power Electronics, vol. 3, no. 3, pp. 1193-1204, Dec. 2015. [Baidu Scholar] 

26

B. Gao, Y. Wang, S. Zeng et al., “Analysis of sub-synchronous component path and damping characteristics of D-PMSG-based wind farm incorporated into weak AC grid,” Proceedings of the CSEE, vol. 42, no. 14, pp. 5089-5103, Jul. 2022. [Baidu Scholar] 

27

L. Liu, Y. Wang, Y. Liu et al., “Analysis of sub-synchronous interaction mechanism between D-PMSG based wind farm and LCC-HVDC,” in Proceedings of 2021 IEEE Sustainable Power and Energy Conference, Nanjing, China, Dec. 2021, pp. 203-210. [Baidu Scholar] 

28

B. Gao, P. Deng, Y. Wang et al., “Evaluation of damping of subsynchronous interaction between direct-drive wind farm and LCC-HVDC based on the damping path analysis,” International Journal of Electrical Power &Energy Systems, vol. 144, pp. 108532-108542, Jan. 2023. [Baidu Scholar] 

29

B. Gao, Y. Liu, R. Song et al., “Study on subsynchronous oscillation characteristics of DFIG-based wind farm integrated with LCC-HVDC system,” Proceedings of the CSEE, vol. 40, no. 11, pp. 3477-3489, Jun. 2020. [Baidu Scholar] 

30

B. Gao, Y. Liu, B. Shao et al., “A path analysis method to study the subsynchronous oscillation mechanism in direct-drive wind farm with VSC-HVDC system,” International Journal of Electrical Power & Energy Systems, vol. 142, pp. 108328-108341, May 2022. [Baidu Scholar] 

31

H. Weng, Y. Xu, and Z. Wang, “The impact of steam-turbine governor system on the low frequency oscillation of power grids,” Southern Power System Technology, vol. 8, no. 3, pp. 83-86, Jun. 2014. [Baidu Scholar] 

32

Y. Xu, M. Zhang, L. Fan et al., “Small-signal stability analysis of type-4 wind in series-compensated networks,” IEEE Transactions on Energy Conversation, vol. 35, no. 1, pp. 529-538, Mar. 2018. [Baidu Scholar] 

33

S. Zhao, N. Wang, R. Li et al., “Sub-synchronous control interaction between direct-drive PMSG-based wind farms and compensated grids,” International Journal of Electrical Power & Energy Systems, vol. 109, pp. 609-617, Jul. 2019. [Baidu Scholar]